Defiant nc clearance chart for 8” connections only – Vermont Casting 1610 User Manual

Page 15

background image

15

Defiant 1610 Non-Catalytic Woodburning Stove

30002850

Defiant NC Clearance Chart for 8” Connections ONLY

Stove Clearance

1

Stove Installed

Parallel to Wall

Unprotected Surfaces

Protected Surfaces

Side

Rear

Corners Side Rear

2

Corners

Chimney Connector Clearance

Unprotected Vertical Surfaces Protected Vertical Surfaces

Single-wall connector

Clearance to Combustibles in Front of Stove

48” (1219 mm)

29¹⁄₂” (749 mm)

9¹⁄₂” (241 mm)

All Installations

Stove Installed
Parallel to Wall

Stove

in

Corner

Stove

in

Corner

Top exit with no

connector heat shields.

Flue collar shield installed

Single-wall connector

with shields

(G) 26”

4

(H) 17”

4

(I) 25”

4

(J) 11”

(K) 15”

(L) 9”

(660 mm)

(430 mm)

(635 mm)

(279 mm)

(381 mm)

(229 mm)

(A) 24”

3

(B) 35”

3

(C) 25”

3

(D) 11”

(E) 15”

(F) 9”

(610 mm)

(889 mm)

(635 mm)

(279 mm)

(381 mm)

(229 mm)

Top exit double-wall

chimney connector*. Flue

collar shield installed

Top exit with heat shields

on connector. Flue collar

shield installed

Single-wall connector

(Horizontal)

11¹⁄₂” (292 mm)

9¹⁄₂” (241 mm)

16¹⁄₂” (419 mm)

5¹⁄₂” (140 mm)

* Using a listed double wall oval to round connector.

Rear exit

(S) 21”

(T) 21”

N/A

(U) 8”

(V) 21”

N/A

(533 mm)

(533 mm)

(203 mm)

(533 mm)

(M) 25”

(N) 22”

(O) 14”

(P) 8”

(Q) 11”

(R) 6”

(635 mm)

(559 mm)

(356 mm)

(203 mm)

(279 mm)

(152 mm)

Double-wall chimney

connector

Unprotected Ceiling Surfaces Protected Ceiling Surfaces

30” (762 mm)

19” (483 mm)

1. Most installations require a ceiling heat shield 24” (610 mm) in diameter and suspended 1” (25 mm) from the ceiling that must

surround the pipe when the chimney penetrates the ceiling. Refer to Notes 3 and 4 below for the only exceptions to this. The
ceiling heat shield is always required if clearances are reduced using wall protection.

2. With protected wall surfaces, the rear clearance must be increased by 3” (76 mm) if the flue collar heat shield is not used. The

flue collar shield is required when using connector pipe shields and always with unprotected surfaces.

3. In installations where the ceiling height is 9 feet (2.7 m) or more and if wall protection is not used, the ceiling heat shield is not

necessary.

4. Connector pipe heat shields must extend the entire length of the connector pipe up to 9 feet (2.7 m). In installations where the

ceiling height is 10 feet (3 m) or more and if wall protection is not used, the ceiling heat shield is not necessary.

A minimum ceiling height of 8 feet (2.4 m) measured from the base of the stove is required for all installations.