beautypg.com

Defiant 1610 non-catalytic woodburning stove – Vermont Casting 1610 User Manual

Page 13

background image

13

Defiant 1610 Non-Catalytic Woodburning Stove

30002850

An unprotected mantel (“A”, Fig. 15) cannot be more
than 9” (230 mm) deep and must have a minimum
clearance of 41” (1041 mm), measured from the stove’s
top plate. With a ventilated shield, this clearance may
be reduced safely to 29” (737 mm).
Unprotected top trim (B) protruding 3/4” (19 mm) or less
from the face of the fireplace must be a minimum of 28”
(711 mm) from the stove’s top surface. With a ventilated
trim shield, this clearance may be reduced safely to 21”
(533 mm).
Unprotected side trim (C) that protrudes 3/4” (19 mm) or
less from the face of a fireplace must have a minimum
clearance of 14” (356 mm), measured from the stove’s
top side edge. If the trim extends more than 3/4” (19
mm), it is subject to the requirements for wall clearance.
The charts and sample installations that follow list all
the clearances required for the various installation
configurations of the Defiant.

ST253b
Encore
trim clearances
02/01 djt

A

B

D

C

C

Unprotected

Protected

A. Mantel

41” (1041 mm)

29” (737 mm)

B. Top Trim

28” (711 mm)

21” (533 mm)

C. Side Trim

14” (356 mm)

14” (356 mm)

D. Side Wall

26” (660 mm)

14” (356 mm)

Fireplace and Mantel Trim Clearances

ST253b

Fig. 15 Maintain clearances to combustible components of
the mantelpiece.

Side Wall