Defiant nc clearance chart for 6” connections only – Vermont Casting 1610 User Manual

Page 14

background image

14

Defiant 1610 Non-Catalytic Woodburning Stove

30002850

Defiant NC Clearance Chart for 6” Connections ONLY

Stove Clearance

Stove Installed

Parallel to Wall

Unprotected Surfaces

Protected Surfaces

1

Side

Rear

Corners Side Rear

3

Corners

Chimney Connector Clearance

Unprotected Vertical Surfaces Protected Vertical Surfaces

Single-wall connector

Clearance to Combustibles in Front of Stove

48” (1219 mm)

26¹⁄₂” (673 mm)

21¹⁄₂” (546 mm)

All Installations

Stove Installed
Parallel to Wall

Stove

in

Corner

Stove

in

Corner

Top exit with no

connector heat shields.

Flue collar shield installed

Single-wall connector

with shields

(G) 26”

(H) 18”

(I) 27”

(J) 13”

(K) 26”

(L) 20”

(660 mm)

(457 mm)

(686 mm)

(330 mm)

(660 mm)

(508 mm)

(A) 26”

(B) 31”

(C) 27”

(D) 13”

(E) 26”

(F) 20”

(660 mm)

(787 mm)

(686 mm)

(330 mm)

(660 mm)

(508 mm)

Top exit double-wall chim-

ney connector*. Flue collar

shield installed

Top exit with heat shields

on connector. Flue collar

shield installed.

2

Single-wall connector

(Horizontal)

13¹⁄₂” (343 mm)

21¹⁄₂” (546 mm)

18¹⁄₂” (470 mm)

17¹⁄₂“ (445 mm)

* Using a listed double wall oval to 6” round connector.

Rear exit

(S) 24”

(T) 21”

N/A

(U) 10”

(V) 21”

N/A

(610 mm)

(533 mm)

(254 mm)

(533 mm)

(M) 26”

(N) 23”

(O) 16”

(P) 10”

(Q) 22”

(R) 17”

(660 mm)

(584 mm)

(706 mm)

(254 mm)

(559 mm)

(432 mm)

Double-wall chimney

connector

Unprotected Ceiling Surfaces Protected Ceiling Surfaces

15” (381 mm)

Not measured

1. When wall protection is used, a ceiling heat shield, 24” (610 mm) in diameter and suspended 1” (25 mm) from the ceiling must

surround the pipe in installations where the chimney penetrates the ceiling.

2. The connector pipe heat shield must extend 36” (914 mm) above the flue collar. When this shield is used, a single wall pipe may

continue vertically unshielded.

3. With protected wall surfaces, the rear clearance must be increased by 3” (76 mm) if the flue collar heat shield is not used. The

flue collar shield is required when using connector pipe shields and always with unprotected surfaces.

A minimum ceiling height of 8 feet (2.4 m) measured from the base of the stove is required for all installations.