EFCO CORPORATION 6/2012 PART NO. Y350

Page 10 of 16

Series 5900 Outside Glazed Curtain Wall Installation Instructions

Section VI: Joint Plug Application

Joint Plug Application

A.)

Install the thermal isolator (70
Durometer) in the vertical mullion.

Run continuously and butt joint as

required with sealant.



B.)

Seal vertical gasket raceway X 1” high prior to installation of
joint plugs.














Note: All thermal isolators

should be removed from
the reels and allowed to
shrink prior to installation.

Install thermal isolator

prior to installing the

mullion plug.

Prior to installing the
mullion plugs, seal all three

sides of the pocket, making

sure all cavities are filled.

With sealant in place, mullion plugs

can be installed. Note the mull plug

is applied so that notch is located at

the pressure plate gasket location.

(Seal all three corresponding sides
of mullion plug before installation so

sealant on mullion plug will marry to

sealant that is placed in the pocket.)