Optional economi$er iv, Table 27 — fan rpm at motor pulley settings – Carrier SINGLE PACKAGE ROOFTOP UNITS 48PG20-28 User Manual
Page 39

39
Table 26 — Accessory/FIOP Static Pressure (in. wg)* — 48PG20-28
LEGEND
*The static pressure must be added to the external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.
Table 27 — Fan Rpm at Motor Pulley Settings*
LEGEND
*Approximate fan rpm shown.
NOTE: Factory pulley speed setting is at 3 turns open.
Optional EconoMi$er IV —
See Fig. 23 for EconoMi$er
IV component locations. The optional EconoMi$er IV comes
from the factory fully wired and assembled. No field wiring or
assembly is required for standard outdoor dry bulb changeover
operation. Field wiring of accessory sensors is required for
different operational modes.
ECONOMI$ER IV STANDARD SENSORS
Outdoor Air Temperature (OAT) Sensor — The outdoor air
temperature sensor is a 10 to 20 mA device used to measure the
outdoor-air temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling. The sensor is factory-installed on the EconoMi$er IV
in the outdoor airstream. See Fig. 24. The operating range of
temperature measurement is 40 to 100 F.
Mixed-Air Temperature (MAT) Sensor — The mixed-air
temperature sensor is a 3 K thermistor located at the outlet of
the indoor fan. See Fig. 24. This sensor is factory installed. The
operating range of temperature measurement is 0° to 158 F.
The temperature sensor is a short probe with blue wires
running to it.
Outdoor Air Lockout Sensor — The Economi$er IV is
equipped with an ambient temperature lockout switch located
in the outdoor airstream which is used to lock out the compres-
sors below a 42 F ambient temperature.
ECONOMI$ER IV CONTROLLER WIRING AND OPER-
ATIONAL MODES — Determine the EconoMi$er IV control
mode before set up of the control. Some modes of operation may
require different sensors. Refer to Table 28. The EconoMi$er IV
is supplied from the factory with a mixed-air temperature
sensor and an outdoor air temperature sensor. This allows for
operation of the EconoMi$er IV with outdoor air dry bulb
changeover control. Additional accessories can be added to
allow for different types of changeover control and operation
of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover — The standard controller is
shipped from the factory configured for outdoor dry bulb
changeover control. The outdoor air and mixed-air temperature
sensors are included as standard. For this control mode, the out-
door temperature is compared to an adjustable set point selected
on the control. If the outdoor-air temperature is above the set
point, the EconoMi$er IV will adjust the outdoor-air dampers to
minimum position. If the outdoor-air temperature is below the
set point, the position of the outdoor-air dampers will be con-
trolled to provided free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiometer
will be on. The changeover temperature set point is controlled
by the free cooling set point potentiometer located on the con-
trol. The scale on the potentiometer is A, B, C, and D. See
Fig. 25 for the corresponding temperature changeover values.
COMPONENT
CFM
4,000
4,500
5,000
5,500
6,000
6,500
7,000
7,500
8,000
Economizer
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
COMPONENT
CFM
8,500
9,000
9,500
10,000 10,500 11,000 11,500 12,000
Economizer
0.11
0.12
0.13
0.15
0.16
0.17
0.19
0.20
FIOP
—
Factory-Installed Option
UNIT
48PG
DRIVE
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
20 and 24
(230 and 460 volt)
Low
685
706
727
749
770
791
812
833
854
876
897
918
939
Mid-Low
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Mid-Low
896
924
951
979
1006
1034
1062
1089
1117
1144
1172
1199
1227
Mid-High
1113
1138
1163
1188
1213
1238
1264
1289
1314
1339
1364
1389
1414
High
1096
1116
1137
1157
1177
1197
1218
1238
1258
1278
1299
1319
1339
20 and 24
(575 volt)
Low
751
768
785
802
819
836
853
869
886
903
920
937
954
Mid-Low
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Mid-Low
873
893
912
932
951
971
991
1010
1030
1049
1069
1088
1108
Mid-High
1113
1138
1163
1188
1213
1238
1264
1289
1314
1339
1364
1389
1414
High
1096
1116
1137
1157
1177
1197
1218
1238
1258
1278
1299
1319
1339
28
(all voltages)
Low
687
703
718
734
749
765
780
796
811
827
842
858
873
Mid-Low
805
822
839
856
872
889
906
923
940
957
973
990
1007
Mid-High
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low
687
703
718
734
749
765
780
796
811
827
842
858
873
Mid-Low
805
822
839
856
872
889
906
923
940
957
973
990
1007
Mid-High
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
n/a — not available