Carrier SINGLE PACKAGE ROOFTOP UNITS 48PG20-28 User Manual
Page 33

33
Table 19 — Fan Performance — 48PGF24 — Horizontal Supply and Return Units
LEGEND
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5,500
952
3.38
1003
3.32
1053
3.70
1100
4.09
1145
4.49
6,000
1029
3.74
1077
4.15
1123
4.56
1167
4.98
1210
5.41
6,500
1106
4.67
1151
5.11
1194
5.56
1236
6.01
1276
6.47
7,000
1184
5.75
1226
6.23
1266
6.71
1306
7.19
1344
7.68
7,500
1262
7.00
1302
7.50
1340
8.01
1377
8.53
—
—
8,000
1341
8.41
1378
8.95
—
—
—
—
—
—
8,500
—
—
—
—
—
—
—
—
—
—
9,000
—
—
—
—
—
—
—
—
—
—
9,500
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5,500
1189
4.90
1232
5.31
1273
5.72
1313
6.15
1352
6.58
6,000
1251
5.85
1292
6.29
1331
6.74
1369
7.19
—
—
6,500
1315
6.94
1354
7.41
1391
7.89
—
—
—
—
7,000
1381
8.18
—
—
—
—
—
—
—
—
7,500
—
—
—
—
—
—
—
—
—
—
8,000
—
—
—
—
—
—
—
—
—
—
8,500
—
—
—
—
—
—
—
—
—
—
9,000
—
—
—
—
—
—
—
—
—
—
9,500
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
Bhp — Brake Horsepower Input to Fan
F
F
F
F
G
G
G
G
G
G
G
G
H
H
H
H
H
H
H
H
H