beautypg.com

Carrier PTACSTAT-NP-HP User Manual

Page 14

background image

14

Option 11 -- Minimum Deadband Between Heating And Cooling
Selections:

01 through 06 — Default is 02.

Sets the minimum allowable number of degrees between heating and cooling

setpoints. One setpoint will “push” the other to maintain this difference.
Option 13 -- Room Air Temperature Offset
Selections:

--5 to 5_ F — Default is 0.

This option selects the number of degrees F to be added to the displayed

temperature to calibrate or deliberately miscalibrate the measured room
temperature.
Option 16 -- Maximum Cycles Per Hour
Selections:

2, 4, or 6 — Default is 4.

The maximum cycle rate is limited by internal timers to the selected number of

cycles per hour. Selection of a higher number causes faster cycling, resulting in
more constant room temperature.
Based on the selection of 2, 4, or 6 cycles per hour, a timer is set to 30, 15, or 10

minutes. This much time must elapse from the start of one cycle before another
cycle can start. For testing, it can be defeated for one cycle by simultaneously

pressing the FAN and UP keys.
If the cycle timer is preventing the equipment from turning on, the display icons

that show the equipment is operating will be flashing to indicate a turn--on delay
is present.

This manual is related to the following products: