beautypg.com

Dell UPS 1920T User Manual

Page 76

background image

76

|

MIB Objects

Table 15. Product Physical Group Variables (continued)

Trap Name, Description, and Relative XML Object Path

Trap Level

Trap

trapDCLinkImbalance

DC link imbalance (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced = 1

73

1

trapDCLinkImbalanceOk

DC link imbalance ok

UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced = 0

74

1

trapABMOn (physicalBatteryABMStatus)

ABM state on

Variable: physicalBatteryABMStatusUPS.BatterySystem.Charger.Mode ? 5

79

2

trapABMOff

ABM state off

UPS.BatterySystem.Charger.PresentStatus.Used = 0

80

2

trapLoadSegment1Off

Load segment 1 off

UPS.BatterySystem.Charger.PresentStatus.Used = 0 AND UPS.BatterySystem.Charge.Mode=5

81

2

trapLoadSegment1On

Load segment 1 on

UPS.OutletSystem.Outlet[2].PresentStatus.SwitchOnOff = 1

82

2

trapLoadSegment2Off

Load segment 2 off

UPS.OutletSystem.Outlet[3].PresentStatus.SwitchOnOff = 0

83

2

trapLoadSegment2On

Load segment 2 on

UPS.OutletSystem.Outlet[3].PresentStatus.SwitchOnOff = 1

84

2

trapInHighEfficiencyMode

In High Efficiency mode

UPS.PowerConverter.Input[5].PresentStatus.Used = 1

85

2

trapReturnFromHighEfficiencyMode

Return from High Efficiency mode

UPS.PowerConverter.Input[5].PresentStatus.Used = 0

86

1

trapRectifierOverload

Rectifier input over current

UPS.PowerConverter.Rectifier.PresentStatus.OverLoad = 1

87

2