beautypg.com

Dell UPS 5600R User Manual

Page 60

background image

60

|

MIB Objects

Table 11. IETF UPS MIB Objects (continued)

Variable Name and Relative XML Object Path

Variable Unit

Variable Type

OID

upsEstimatedMinutesRemaining

UPS.PowerSummary.RunTimeToEmpty

1.2.3

Integer

Min

upsEstimatedChargeRemaining

UPS.PowerSummary.RemainingCapacity

1.2.4

Integer

%

upsBatteryVoltage

UPS.PowerSummary.Voltage

1.2.5

Integer

0.1V

upsBatteryCurrent

UPS.PowerSummary.Current

1.2.6

Integer

0.1A

upsBatteryTemperature

UPS.BatterySystem.Battery.Temperature

1.2.7

Integer

°

C

upsInputLineBads

No Relative XML Object Path

1.3.1

Counter

upsInputNumLines

No Relative XML Object Path

1.3.2

Integer

upsInputFrequency

UPS.PowerConverter.Input[1].Frequency

1.3.3.1.2

Integer

0.1 Hz

upsInputVoltage

UPS.PowerConverter.Input[1].Voltage

1.3.3.1.3

Integer

V

upsInputCurrent

UPS.PowerConverter.Input[1].Current

1.3.3.1.4

Integer

0.1 A

upsOutputSource

No Relative XML Object Path

1.4.1

Integer

upsOutputFrequency

UPS.PowerConverter.Output.Frequency

1.4.2

Integer

0.1 Hz

upsOuputNumLines

No Relative XML Object Path

1.4.3

Integer

upsOutputVoltage

UPS.PowerConverter.Output.Voltage

1.4.4.1.2

Integer

V

upsOutputCurrent

UPS.PowerConverter.Output.Current

1.4.4.1.3

Integer

0.1A

upsOutputPower

UPS.PowerConverter.Output.ActivePower

1.4.4.1.4

Integer

W

upsOutputPercentLoad

UPS.PowerSummary.PercentLoad

1.4.4.1.5

Integer

%