beautypg.com

Carrier 30XA080-500 User Manual

Page 2

background image

2

7. Wire the coils of pump contactors (PMP1-A1, A2 and

PMP2-A1, A2) to TB5-11 and 13 (pump 1) and TB5-13

and 15 (pump 2) as shown in Fig. 2 with field-supplied

18 AWG wires and wire terminals.
NOTE: If only one pump is available in the system (no

backup pump), the wiring for PMP2 is not required.

8. Locate the main base board in the main control panel.

Refer to Fig. 3. Near CH18 (J5C) of the board, there are

violet and pink wires tied up outside the wire duct termi-

nated with wire nuts. These wires are for pump auxiliary

contact wiring. Remove the wire nuts and connect the two

wires to the pump auxiliary contacts per Fig. 3 with field-

supplied wiring. Some units may not be supplied with the

J5C connector and the violet and pink wires. A 2-pin con-

nector (Item 8) is supplied if these parts are not present.

Wire the pump contactor auxiliary contacts to the 2-pin

connector. Insert the 2-pin connector into MBB-J5C.
NOTE: If only one pump is available in the system (no

backup pump), the wiring for PMP-2 is not required.

Configuration (All Sizes) —

The control must be

configured for pump control operation. Use the Navigator™ or

the Touch Pilot™ display to configure the system. To configure

the system with the Navigator display, follow the steps below.

1. Set the Enable/Off/Remote switch to OFF position.
2. Press ESCAPE until the Select a Menu Item is displayed

on the screen. Use the arrow key to select the Configura-

tion mode LED.

3. Press ENTER, then use the arrow key to select the

sub-mode ‘OPTN’, press ENTER.

4. Press the down arrow key until ‘PUMP’ is displayed.
5. Press the ENTER key twice. The word ‘PASS’ and

‘WORD’ will flash.

6. Press 0 1 1 1 then ENTER key so that ‘0’ flashes.
7. Use arrow keys to change value to one of the descriptions

in Table 2.

Table 2 — Pump Control Configuration Options

*Used with dual pumps.

8. The unit is now configured for pump control.

To configure the system with the Touch Pilot display, follow

the steps below.

1. Ensure the unit is in Local Off operating mode by looking

at the left upper corner of the group display. If the unit is

not in Local Off mode, push the Start/Stop (0/1) button to

switch it to the Local Off mode.

2. Push the Main Menu button on the bottom line of display,

and then follow the path Config

USER to the USER

table.

3. Scroll down the screen by pushing scroll down button or

page down button until Cooler Pumps Sequence is

displayed. Push Cooler Pumps Sequence and the Point

Data menu will display.

4. Push the Modify button within the Point Data menu. If

the login menu displays, log in with the password of

3333, then press the OK button to confirm the input. The

value of CCN variable cpumpseq will display. Enter 1, 2,

3, or 4 per Table 2 and press the OK button to confirm the

input.

5. Push the Home button. A save confirmation menu will

display. Press the OK button to confirm.

6. The unit is now configured for pump control.

Test Pump Control Output —

Use the Navigator or

Touch Pilot display, the instructions given in the Controls,

Start-Up, Operation Service and Troubleshooting manual and

the Service Test mode to verify proper operation of pump

output. Be sure to turn off the fuse or circuit breaker for the

pump(s) and verify that the pump contactor(s) is being

energized during the test. For the Navigator display, illuminate

the Service Test LED, enter the TEST mode, enable the test

request, (‘T.REQ’) and test outputs (‘PMP.1’, ‘PMP.2’). For the

Touch Pilot display, from the main menu, follow the

Status

QCK_TST1, enable the Quick Test, and test outputs

(‘Water Exchanger Pump 1’, ‘Water Exchanger Pump 2’).

Once the outputs have been tested, the installation is complete.

Return the Enable/Off/Remote contact switch to the desired

position. Restore power to the pumps.

CONFIGURATION

DESCRIPTION

0

No Pump Control

1

1 Pump Only

2

2 Pumps Auto*

3

PMP 1 Manual

4

Pump2 Manual*

TB10-X2 (080-120 SIZES, 460/575 V)
TB11-X2 (ALL OTHER UNITS)

TB10-X1 (080-120 SIZES, 460/575 V)
TB11-X1 (ALL OTHER UNITS)

Fig. 1 — Pump Board 24 V Power Wiring

a30-4444