beautypg.com

Dell UPS 1920T User Manual

Page 58

background image

58

|

Specifications

Table 15. Battery

Configuration

500W: (2) 12V, 7 Ah internal batteries (no EBM)

1000W: (3) 12V, 9 Ah internal batteries; (6) 12V, 9 Ah EBM

1920/1500W: (6) 12V, 9 Ah internal batteries; (12) 12V, 9 Ah EBM

Voltage

500W: 24 Vdc internal

1000W: 36 Vdc internal, 36 Vdc EBM

1920/1500W: 72 Vdc internal, 72 Vdc EBM

Fuses

500W internal battery: (2) 40A fuses

1000W, 1920/1500W internal batteries:

(2) 30A fuses

1000W, 1920W EBMs: (4) 30A fuses

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

Internal batteries: approximately 4 hours to 90% (8 hours for 500W models) usable

capacity at nominal line and no supplementary power supply load

EBMs: approximately 12 hours to 90% from a discharge of 50% rated load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Runtimes

Internal batteries: 5 minutes at full load/14 minutes at half load

UPS with one EBM attached: 19 minutes at full load/45 minutes at half load

*Battery runtimes are approximate and vary depending on the load configuration and battery charge.

DC/DC

Converter

Input
Filter

AVR

Output

Filter

Charger

Battery

DC/AC

Inverter

Figure 27. Line-Interactive UPS Block Diagram