Does

spark stop

when pilot

lights?

24 volts

across

terminals PV

& MV/PV at

module?

Pulsing

Spark

across

ignitor/sensor

gap?

Y

* Module is in soft
lockout. Reset by
momentarily
interupting power to
boiler and waiting for
prepurge.
* Break in spark
cable insulation
* Break in pilot
porcelain
* Incorrect pilot
spark gap
* Loose connection
in spark cable
* Loose ground
connection
* Defective Ignition
Module

N

Pilot

lights?

Y

N

N

* Defective
module

24 volts

across PV &

MV/PV at gas

valve?

* Defective EI
wiring harness.

N

* Loose connection in
ignition cable or
ground wire
* Pilot electrode
porcelain cracked
* Pilot flame not
covering gap
between electrode
and grounding
strap
* Low inlet gas
pressure
* Defective module

Main

burner

lights?

N

Y

24VAC

across

terminals MV

& MV/PV on

module?

Y

N

* Defective
module

24 volts

between MV &

MV/PV on gas

valve?

* Defective
gas valve

*Defective EI
harness

END

START

(24 volts is present across 24V and 24V (GND) on

Ignition Module, 30 second prepurge period has

passed)

N

Y

N

Y

Y

Y

* Low inlet gas pressure
* Plugged, kinked or leaking
pilot tubing
* Plugged pilot orifice
* Gas line not purged of air
* Defective pilot assembly
* Defective gas valve

IMPORTANT: ALL PILOT TROUBLESHOOTING
ON THIS CHART MUST BE PERFORMED AFTER
THE 30 SECOND PREPURGE HAS ENDED AND
BEFORE THE END OF THE 90 SECOND TRIAL
FOR IGNITION PERIOD.

TROUBLESHOOTING CHART FOR IGNITION SYSTEMS USING UT 1003-626A IGNITION MODULE