Crown Boiler CWD138 User Manual

Page 61

background image

59

59

N

Y

Y

Call for heat

from

"DHW/H2"

zone

"DHW/H2"

circulator

start?

Defective

CB502 board

DHW

LED On?

24V across

"DHW/H2" T

and T

* Loose connection in
t'stat or zone valve end
switch wiring
* Defective t'stat or zone
valve end switch
* T'stat or zone system
miswired-consult zone
valve or t'stat
manufacturer's
instructions.

N

120 volts across

blue and white

circulator leads?

*Loose
connection
between boiler
J-box and circ

* Defective "DHW/H2"
relay on CB502
* Relay not fully seated
in socket
* Loose connection in
circulator wiring

Y

N

N

Continued on

next page

Y

TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)
PAGE 2 OF 4