Crown Boiler CWD138 User Manual

Page 62

background image

60

60

120 volts

present?

* Loose
connection at
fan plug or fan
capacitor
* Defective
capacitor
* Defective fan

24 volts present

across yellow

transformer lead and

purple lead on

pressure switch?

*Defective "FAN"
relay
*Defective CB502
board

Continued

from previous

page

Unplug fan and

check for 120V

across H FAN

and N FAN on

CB502 board

*Loose pressure
switch harness
*Defective CB502
board

PRESS

LED on?

FAN

LED on?

LIMIT

LED on?

Fan On?

24V between

brown lead on

limit and yellow

lead on

transformer?

* Boiler water
temp over L4080D
setpoint
*Defective L4080D

* Missing or loose
"RESET CONTROL"
jumper
*Missing or loose
"CN1" jumper
*Defective CB502
board

N

Y

N

N

* Kinked or blocked
vacuum switch tubing
* Defective vacuum
switch

N

Y

Y

N

24 volts present

across yellow

transformer lead and

red lead on pressure

switch?

N

Y

Minimum

pressure at

switch called in

Table 7 present

across switch?

*Tubes reversed on
pressure switch
*Leak in tubes at pressure
switch connection
*Loose pressure switch
harness connection
*Defective CB502 board

Y

N

N

Y

Y

Y

N

Y

TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)