Crown Boiler CWD138 User Manual

Page 60

background image

58

58

120 volts across

black and white

transformer

primary leads ?

Call from

"HEAT 1"

zone

"HEAT 1"

Circulator

start?

* Power off
* Blown fuse or
tripped breaker
* Miswired or
loose electrical
connection in
120 volt line

120 volts

across red and
white circulator

leads?

* Loose connection in
t'stat or zone valve end
switch wiring
* Defective t'stat or zone
valve end switch
* T'stat or zone system
miswired-consult zone
valve or t'stat
manufacturer's
instructions.

N

Y

N

N

Y

N

Y

N

START

(No call for

heat from

either zone)

Y

Y

24volts

transformer

secondary?

* Defective
transformer.

* Loose
connection
between boiler
J-box circ.
* Defective
circulator

* Defective "HEAT 1" relay
on CB502
* Relay not fully seated in
socket

Y

Y

N

Y

N

Y

PWR

LED On?

HEAT

LED On?

"DHW

PRIORITY"

Switch on?

*Defective
transformer
harness
*Defective
CB502

24V across

"HEAT 1" T

and T

"DHW/H2"

zone used?

*Defective CB502
board
*Defective
"DHW/H2" relay

*Defective CB502

board

N

Y

N

TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)
PAGE 1 OF 4