beautypg.com

Mounting information, Approval signature date phone no – Amico Ceiling Column Manual Retractable User Manual

Page 13

background image

Mounting Information

Approval Signature

Date

Phone No.

NOTE: Riser plate to be installed in ceiling with appropriate mounting structure and anti-sway sup-
port. The methods of support shown are provided for information only.

STRUCTURAL CEILING

17” Sq.

[431.8 mm Sq.]

CEILING COVER

(FIELD MOUNTED)

FINISHED CEILING

COLUMN

MOUNTING

PLATE

1/2” [12.7 mm] DIA. MOUNTING BOLTS FUR-
NISHED WITH ROUGH-IN PLATE. TYP. OF 4, See
note 1.

MIN. 13” [330.2 mm] MAX.
16” SQ CEILING CUT-OUT
FOR COLUMN

17” Sq.

[431.8 mm Sq.]

14.75” Sq.

[374.65 mm Sq.]

9.5” Sq.

[241.3 mm Sq.]

RISER
PLATE

ANTI-SWAY SUPPORT STRUCTURE
(SUPPLIED BY OTHERS)

1.00” [25.4 mm]

4.5”

[114.3 mm]

3/4” [19.5 mm] or 7/8” [22.23 mm]
THREADED ROD (X4) (SUPPLIED BY OTHERS)

NOTE:

1. All labour and material for installation of Riser to Mounting Structure supplied by others.

2. General Contractor has fi nal responsibility for the strength and stability of the mounting structure that is supplied

by others.

3. Riser plate to be mounted 4.5” (114.3 mm) above fi nished ceiling.

4. Mounting of column unit to riser plate by (4) 1/2” threaded rods, provided by Amico.

5. Space between top of Riser Plate and structural ceiling must be minimum 10”(254 mm).

6. Riser Pipe(s) extend 8” (203.2 mm) above riser plate.

7. Pre-ship of the riser assembly is available upon customer’s request.

www.amico.com

11