beautypg.com

Ab c, 9 pro-lift trip-reset tine hydraulics – Great Plains SLD600 Operator Manual User Manual

Page 32

background image

32 Simba SLD

602-227M-ENG

2013-02-05

5.9 Pro-Lift Trip-Reset

Tine Hydraulics

The circuit allows for the tines to be

pressurised down into work, whereupon a

relief valve limits this applied tractor down

pressure to a value less than the main system

accumulator (80b x 2 litre). This allows tines

to trip in work, the oil being absorbed by

the main accumulator. A secondary (rod

side) accumulator ensures this side of the

cylinder is maintained full of oil to minimise

cavitation and seal damage. A pre charge

valve restricts return rod side oil flow to the

tractor as the tines are pressurised down

to ensure this secondary circuit is charged.

In operation, oil is locked in the cylinder

circuit at a pressure determined by the relief

valves 90-120 bar full bore side and 0-20 bar

rod side. This occurs at all times, even with

the circuit in float at the tractor, provided the

tines are fully down. For extremely stony

conditions, adjust the valve to read 90 bar

on the gauge as the tines are pressured

down. For heavy soils with little stone

where compaction is present it is possible

to increase this pressure to 120 bar.

If the tine circuit should need setting the

following procedure should be followed (an

assistant will be required):

1

First locate the manifold block; it is

located at the front of the Simba SLD

chassis above the drawbar.

2

Locate the valve on the top face of

the block (A) and undo the lock nut.

Using a 4mm allen key turn the valve

all the way clockwise then turn it

anticlockwise 2 full turns.

3

Locate valve C on the block; undo the

lock nut and turn the valve all the way

clockwise.

4

Locate valve B, undo the lock nut and

turn the valve all the way anticlockwise.

5

Start the tractor and put the spool that

controls the tines into the float position.

Both the gauges will go to zero and the

tines will go down. This indicates that

the system is depressurised.

6

Now get someone to pressure the tines

down. Whilst they are being pressured

down, turn valve B on the block slowly

clockwise. The pressure on the upper

gauge will start to rise. Turn the valve

until you reach approximately 80 to 90

bar (the pressure on the lower gauge

will now be reading approximately 10

to 15 bar). Lock off all the valves. The

tine circuit is now set.

Fig. 5.05: Pro-Lift Tine Hydraulic Manifold

5. Servicing and Maintenance

A

B

C

This manual is related to the following products: