3.
Thoroughly clean tubes immediately after each test to avoid
staining and future contamination.
4.
Ferrous ions, Fe
+2
, will give a false positive. The contribution of Fe
+2
to reading can be determined by testing a second sample and
skipping Step 4. This result should be subtracted from previous
result.
PRO CE DURE
1.
Fill test tube (0106) to the 5 mL line with sample water.
2.
Add 3 drops of *DEHA Reagent 1 (4791) and 3 drops of *DEHA
Reagent 2 (4792).
3.
Cap and mix.
4.
Add 3 drops of *DEHA Reagent 3 (4793). Cap and mix.
NOTE:
If the alkalinity of the sample is over 300 ppm, use the
following number of drops of *DEHA Reagent 3:
Alkalinity, ppm
Drops of
*DEHA Reagent 3
300-399
4
400-499
5
500-599
6
600-699
7
700-799
8
800-899
9
900-999
10
5.
Wait exactly 10 minutes.
6.
Immediately insert test tube into top of Octa-Slide Viewer (1100).
Slide DEHA Octa-Slide Bar (3442) into Octa-Slide Viewer. Match
sample color to a color standard. Record result as ppm DEHA.
NOTE:
This test kit will also test for the oxygen scavenger erythorbic
acid (also called isoascorbic acid or araboascorbic acid). Follow the test
instruction and multiply the results by 4 to get ppm Erythorbic Acid.
DEHA x 4 = Erythorbic Acid