beautypg.com

Exide Technologies Section 95.10 User Manual

Page 6

background image

3.1 CONCEALED DAMAGE

Within 15 days of receipt, examine all batteries for concealed damage. If damage is noted,
immediately request an inspection by the carrier and file a concealed damage claim. Any
delay in notifying carrier may result in loss of right to reimbursement for damages.

SECTION 4 - STORAGE PRIOR TO INSTALLATION

4.0 STORAGE LOCATION

If the battery is not to be installed at the time of receipt, it is recommended that it be
stored indoors in a cool [25°C (77°F)], clean, dry location. Do not stack pallets or
possible battery damage may occur.

4.1 STORAGE INTERVAL

The storage intervals between the date of shipment and the date of initial charge
should not exceed six (6) months. The battery should be given its initial charge (refer to
Section 8) before the end of the above stated storage interval. Storage at elevated
temperatures will result in accelerated rates of self discharge. A general rule of thumb
is that for every 10°C (18°F) increase above 25°C (77°F) the time interval for initial
charge should be halved. For example, if a battery was stored at 35°C (95°F) the initial
charge time interval would be 3 months. If the battery was stored at 30°C (86°F) the
initial charge time interval would be 4.5 months. Storage beyond these periods without
proper charge can result in excessive sulfation of the plates which is detrimental to
battery performance and life.

SECTION 5 - GENERAL INSTALLATION CONSIDERATIONS

Prior to starting the installation of the RELAY GEL battery system, a review of this sec-
tion is strongly recommended.

5.0 BATTERY LOCATION

It is recommended that the battery be installed in a clean, cool, dry location. Floors
should be reasonably level and able to support the battery weight. A location having an
ambient temperature of 25°C (77°F) will result in optimum battery life and performance.
Temperatures below 18°C (65°F) reduce battery efficiency. Temperatures above 27°C
(80°F) will result in a reduction of battery life. Continuous operation above 50°C (122°F)
is not recommended.

A designated aisle space should be provided to permit initial installation and future
service or surveillance of the batteries.

3