SECTION 12 - TAP CONNECTIONS

Tap connections should not be used on a battery. This can reduce battery life.

SECTION 13 - TEMPORARY NON-USE

An installed battery that is expected to stand idle for over 6 months should be treated
as follows:

A. Give the battery an equalizing charge. Following the equalizing charge, open the

connections at the battery terminals to remove charger and load from the battery.

B. Every six months, temporarily connect battery to charger and give an equalizing

charge.

C. To return the battery to normal service, retorque all connections per Section 7.3 and

then re-connect the battery to the charger and return the battery to float operation.

D. If the battery is standing at an elevated temperature, corrections to the time period

to equalize charge should be corrected per Section 4.1.

SECTION 14 - UNIT CLEANING

Periodically clean unit covers to remove accumulated dust. If any unit or parts appear to
be damp with electrolyte or show signs of corrosion, clean with a solution of baking
soda and water or isopropyl alcohol, and re-examine within 30 days to determine if the
condition re-occurs. If so, contact your local GNB representative.

13

Do not clean plastic parts with any solvents, detergents, mineral

spirits, or spray-type cleaners other than those mentioned here as

these can cause crazing or cracking of the plastic materials.

CAUTION