2 power requirements, 3 site wiring requirements, Power requirements – Unitec Portal Site Planning & Base User Manual
Page 10: Site wiring requirements
P O R T A L T I
Site Planning and Base Installation for Portal TI Units
6
Document #: PTL1008
1.4.2 Power
Requirements
The Portal requires 120 VAC, 8 Amps service. In applications where barrier gates
are to be used, each gate requires 120 VAC, 5 Amps service. The Portal and Gate
must be powered from separate circuits.
Note:
Ensure the protective earth ground wires do not carry any motor return current. Only
the neutral wire should carry return current. Follow local electrical code when wiring
the Portal TI.
1.4.3
Site Wiring Requirements
Wiring requirements will vary by site depending on the type of wash equipment and
the Portal configuration. The following table shows site wiring, which may be needed.
As wires are pulled through conduit, ensure there is at least 6 ft. of wire extending
from the end of the conduit stub.
Circuit Description
Wire Qty
Wire Requirements
Portal Power (115-120 VAC, 8 Amps).
3
16 AWG minimum, black/white/green
Gate Power (115-120 VAC, 5 Amps).
3
16 AWG minimum, black/white/green
Network connection (to router)
1
Cat 5 communications cable, 295 ft max length
Wash Signaling (required if the Portal will be
connected to the wash controller)
Varies
Refer to wash equipment manufacturer’s
instructions
Phone Line
(required for dial-up credit option)
1
2 Pair / 4 Conductor Telephone Cable
Intercom
(Required to interface with site intercom)
4
22 AWG minimum
Camera
(Required for Portal camera option)
1
Type RG59/U coaxial cable
Gate Control – from gate controller to Portal
(Required if gate controller is used)
4
18 AWG minimum
Gate Control - from gate controller to gate
(Required if gate controller is used)
3
18 AWG minimum
Gate Control – from Portal to Gate
(Required if gate is used without gate controller)
4
18 AWG minimum
RFID Option
(from RFID Antenna to Portal)
1
Cable is supplied with RFID kit