Sequence of Operation

24 V (ac) Powered Outputs

The 335 has an internal transformer that provides
powered outputs for up to six 24 V (ac) zone valves and
six thermostats.

The internal transformer has limited power available. Refer
to the Job Records to determine the load on the transformer.
If the load is too large for the transformer, refer to the Wiring
Brochure to add additional power to the system.

115 V (ac) Powered Outputs

The 335 has an internal relay that provides a powered
output for a zone group pump.

Refer to the Job Records to determine the allowable loads
for this relay.

Sequence of Operation

When a thermostat calls for heat, the Zone LED turns on
and power is supplied to the zone valve.

If the Zone Group Pump DIP switch is set to On and the

Zone Group Pump Delay DIP switch is set to Off, the
Zone Group Pump LED and relay turn on.

If the Zone Group Pump DIP switch is set to On and the

Zone Group Pump Delay DIP switch is set to On, the
Zone Group Pump LED and relay turn on three minutes
after the zone valve is powered.

If the Zone Group Pump DIP switch is set to Off, the

Zone Group Pump LED and relay are not turned on.

Pump A Demand

To operate the Zone Group Pump A relay externally, a
powered signal must be sent to the Pmp A terminal on the
335. Refer to the Wiring Brochure for the proper wiring.

24 V (ac) R & C

tN4 Bus A

115 V (ac) L & N

Zone Manager 335

Meets Class B:
Canadian ICES &
FCC Part 15

Made in Canada

Zone A1

Zone A2

Power

Zone Group Pump A

Zone A3

Zone A4

Zone A5

Zone A6

tN4

tektra 996-01

For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.5 A

Caution! Disconnect All
Power before Opening

Limited power available, see wiring brochure

For product literature:
www.tekmarcontrols.com

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

20

H7003B

32

33

34

35

36

37

38

39

40

41

42

43

17

18

19

21

22

23

24

25

26

27

24 V (ac) Fuse: T2.5 A 250 V

28

29

30

31

On/Off

Zone Group

Pump A Delay

Zone Group

Pump A

A1
A2
A3
A4
A5
A6
A1
A2
A3
A4
A5
A6

tN4

C

C

C

W

W

R

R

Pmp tN4

tN4

C

W

R

tN4

C

W

R

R

tN4

C

W

tN4

R

C

W

tN4

Input Power

Zone Group

Zone A1

Zone A2

Zone A3

Zone A4

Zone A5

Zone A6

Zn Grp A

A

tNt

Zone A1

tNt

Zone A2

tNt

Zone A3

tNt

Zone A4

tNt

Zone A5

tNt

Zone A6

N

L

N

Pmp A

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

Supply /signal wires 90°C min.