Sequence of operation, 24 v (ac) powered outputs, 115 v (ac) powered outputs – tekmar 335 Zone Manager User Manual
Page 2: Pump a demand
© 2005
D 335 - 06/05
2 of 4
Sequence of Operation
24 V (ac) Powered Outputs
The 335 has an internal transformer that provides
powered outputs for up to six 24 V (ac) zone valves and
six thermostats.
The internal transformer has limited power available. Refer
to the Job Records to determine the load on the transformer.
If the load is too large for the transformer, refer to the Wiring
Brochure to add additional power to the system.
115 V (ac) Powered Outputs
The 335 has an internal relay that provides a powered
output for a zone group pump.
Refer to the Job Records to determine the allowable loads
for this relay.
Sequence of Operation
When a thermostat calls for heat, the Zone LED turns on
and power is supplied to the zone valve.
•
• If the Zone Group Pump DIP switch is set to On and the
Zone Group Pump Delay DIP switch is set to Off, the
Zone Group Pump LED and relay turn on.
•
• If the Zone Group Pump DIP switch is set to On and the
Zone Group Pump Delay DIP switch is set to On, the
Zone Group Pump LED and relay turn on three minutes
after the zone valve is powered.
•
• If the Zone Group Pump DIP switch is set to Off, the
Zone Group Pump LED and relay are not turned on.
Pump A Demand
To operate the Zone Group Pump A relay externally, a
powered signal must be sent to the Pmp A terminal on the
335. Refer to the Wiring Brochure for the proper wiring.
24 V (ac) R & C
tN4 Bus A
115 V (ac) L & N
Zone Manager 335
Meets Class B:
Canadian ICES &
FCC Part 15
Made in Canada
Zone A1
Zone A2
Power
Zone Group Pump A
Zone A3
Zone A4
Zone A5
Zone A6
tN4
tektra 996-01
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.5 A
Caution! Disconnect All
Power before Opening
Limited power available, see wiring brochure
For product literature:
www.tekmarcontrols.com
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
20
H7003B
32
33
34
35
36
37
38
39
40
41
42
43
17
18
19
21
22
23
24
25
26
27
24 V (ac) Fuse: T2.5 A 250 V
28
29
30
31
On/Off
Zone Group
Pump A Delay
Zone Group
Pump A
A1
A2
A3
A4
A5
A6
A1
A2
A3
A4
A5
A6
tN4
C
C
C
W
W
R
R
Pmp tN4
tN4
C
W
R
tN4
C
W
R
R
tN4
C
W
tN4
R
C
W
tN4
Input Power
Zone Group
Zone A1
Zone A2
Zone A3
Zone A4
Zone A5
Zone A6
Zn Grp A
A
tNt
Zone A1
tNt
Zone A2
tNt
Zone A3
tNt
Zone A4
tNt
Zone A5
tNt
Zone A6
N
L
N
Pmp A
C
Vlv
C
Vlv
C
Vlv
C
Vlv
C
Vlv
C
Vlv
Supply /signal wires 90°C min.