Sequence of Operation

24 V (ac) Powered Outputs

The 325 has an internal transformer that provides
powered outputs for up to six 24 V (ac) zone valves and
six thermostats.

The internal transformer has limited power available. Refer
to the Job Records to determine the load on the transformer.
If the load is too large for the transformer, refer to the Wiring
Brochure to add additional power to the system.

115 V (ac) Powered Outputs

The 325 has an internal relay that provides a powered
output for a zone group pump.

Refer to the Job Records to determine the allowable loads
for this relay.

Sequence of Operation

When a thermostat calls for heat, the Zone LED turns on
and power is supplied to the zone valve.

If the Zone Group Pump DIP switch is set to On and the

Zone Group Pump Delay DIP switch is set to Off, the
Zone Group Pump LED and relay turn on.

If the Zone Group Pump DIP switch is set to On and the

Zone Group Pump Delay DIP switch is set to On, the
Zone Group Pump LED and relay turn on three minutes
after the zone valve is powered.

If the Zone Group Pump DIP switch is set to Off, the

Zone Group Pump LED and relay are not turned on.

115 V (ac) L & N

N

Zone Group

89

90

Pmp C

tN4

Meets Class B:
Canadian ICES &
FCC Part 15

5 A (max)

Zone Expansion Module 325

tektra 998-01

Relay Rating: 115 V (ac) 5 A

24 V (ac) Fuse: T2.5 A 250 V

Power

Zone Group Pump C

H7001B

Zone C1

Zone C2

Zone C3

Zone C4

Zone C5

Zone C6

51

52

53

54

55

56

57

58

59

60

61

62

C

C

W

W

R

R

tN4

tN4

C

W

R

tN4

tNt

Zone C1

tNt

Zone C2

tNt

Zone C3

63

64

65

66

67

68

69

70

71

72

73

74

C

C

W

W

R

R

tN4

tN4

C

W

R

tN4

tNt

Zone C4

tNt

Zone C5

tNt

Zone C6

75

76

tN4

C

Zn Grp C

C2
C3

On/Off

Zone Group

Pump C Delay

Zone Group

Pump C

C4
C5
C6

C5
C6
C1

C1

C3

C2

C4

Limited power available, see wiring brochure

77

78

79

80

81

82

83

84

85

86

87

88

Zone C1

Zone C2

Zone C3

Zone C4

Zone C5

Zone C6

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

Made in Canada