Demand Inputs
Three Demand Inputs
The 3 demand inputs allow a third party device to select a 
scene for the tN4 system. The third party device could be 
an automation system or a telephone switch with dry relay 
contacts or a 24 V (ac) powered output. The third party 
device output connects to one or more of the 480 demand 
inputs. The tN4 operating scene is changed according to 
the demand inputs listed on the following table:
The third party device must close the relay contacts 
permanently in order for the user switch to remain in a 
particular scene. Once the relay contacts are all opened, the 
user switch changes back to scene 1 (normal scene). The 
user switch demand input is not compatible with momentary 
contact closure on third party devices.
Important Note:
A scene change from any tN4 device overrides the operation 
of the demand inputs. This includes the user buttons on 
the user switch, or changing the scene number on any 
tN4 thermostat or tN4 setpoint control. When the scene is 
changed, the user switch will ignore the demand inputs until a 
new demand input combination is made. It is recommended 
that the third party’s relay contact be opened before the 
user switch responds to further demand inputs.
For a list of suggested third party devices that can connect 
to the user switch, please contact your tekmar sales 
representative.
Application Examples:
A third party telephone switch has a normally open contact 
that connects to the User Switch demand 1 input. This 
allows a user to place a telephone call to the telephone 
switch to change the tN4 system from Scene 1 (Normal) 
to Scene 2 (Away). To change the tN4 system from 
Scene 2 (Away) back to Scene 1 (Normal), either press 
the user switch button to return to Scene 1 or place a 
call to the telephone switch. If the user switch button is 
used, a call still must be placed to the telephone switch 
to open the relay contact.
Power: 24 V ± 10% 50/60 Hz 2.2 VA
Demands: Contact Closure or 24 V (ac)
tN4 User Switch 480
Three Inputs
Made in Canada
1009-01
For product instructions see brochure
Use at least 167°F (75°C) conductors
Meets Class B:
• Canadian ICES
• FCC Part 15
Com
2 1
3
Dem
Demand
R
C
tN4
Telephone Switch
Normally
Open Relay
A third party automation system has three normally open 
contacts that connect to the User Switch demand inputs 
1, 2, and 3. This allows a user to change the operating 
scene of the tN4 system from the automation display.
Scene
1
2
3
4
5
6
7
8
Contact 1
Off
On
Off
On
Off
On
Off
On
Contact 2
Off
Off
On
On
Off
Off
On
On
Contact 3
Off
Off
Off
Off
On
On
On
On