beautypg.com

Detailed cooling capacities* continued – Bryant DE LUXE 12 SEER 552A User Manual

Page 32

background image

—32—

DETAILED COOLING CAPACITIES* Continued

NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.

* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or

indoor unit is located above outdoor unit, a slight variation in capacity may occur.

† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).

** Total unit kW is total of indoor and outdoor unit kilowatts.

†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.

EVAP

AIR

CONDENSER ENTERING AIR TEMPERATURES °F

75

85

95

105

115

125

CFM

EWB

Capacity

MBtuh†

Total

Sys

kW**

Capacity

MBtuh†

Total

Sys

kW**

Capacity

MBtuh†

Total

Sys

kW**

Capacity

MBtuh†

Total

Sys

kW**

Capacity

MBtuh†

Total

Sys

kW**

Capacity

MBtuh†

Total

Sys

kW**

Total Sens‡

Total Sens‡

Total Sens‡

Total Sens‡

Total Sens‡

Total Sens‡

552AN060-F Outdoor Section With CK5A/CK5BA060 Indoor Section

1600

72

66.5

32.5

4.51

64.0

31.7

5.03

61.2

30.7

5.60

57.9

29.6

6.25

54.3

28.3

6.97

50.2

27.0

7.76

67

62.4

41.9

4.44

59.6

40.8

4.95

56.4

39.5

5.50

53.0

38.2

6.13

49.5

36.9

6.83

43.3

34.5

7.53

63†† 55.7

39.9

4.33

52.2

38.3

4.81

48.5

36.7

5.34

46.5

35.9

5.97

43.7

34.7

6.66

38.4

32.5

7.35

62

54.4

49.4

4.31

51.0

47.8

4.79

47.5

46.1

5.32

45.7

45.1

5.95

43.7

43.7

6.66

39.9

39.9

7.41

57

51.3

51.3

4.25

48.4

48.4

4.74

47.0

47.0

5.30

45.4

45.4

5.94

43.4

43.4

6.65

39.6

39.6

7.40

1800

72

67.2

33.5

4.60

64.8

32.7

5.12

61.9

31.8

5.70

58.6

30.8

6.35

54.6

29.4

7.03

50.5

28.1

7.82

67

62.9

43.6

4.52

60.1

42.6

5.02

57.0

41.5

5.59

53.7

40.3

6.22

50.1

39.1

6.92

44.0

36.7

7.64

63†† 58.6

42.9

4.46

55.0

41.3

4.94

51.2

39.7

5.47

49.2

38.8

6.11

44.4

36.8

6.76

39.2

34.7

7.47

62

57.5

53.4

4.44

54.0

51.7

4.92

50.6

50.0

5.46

48.8

48.8

6.10

45.6

45.6

6.79

41.6

41.6

7.55

57

54.7

54.7

4.39

51.8

51.8

4.88

50.2

50.2

5.45

48.5

48.5

6.10

45.6

45.6

6.79

41.6

41.6

7.55

2000

72

67.6

34.3

4.68

65.3

33.7

5.21

62.4

32.9

5.79

58.6

31.6

6.42

55.0

30.5

7.13

50.9

29.2

7.92

67

63.6

45.4

4.61

60.7

44.5

5.12

57.6

43.5

5.68

54.3

42.4

6.32

50.7

41.2

7.02

44.4

38.8

7.74

63†† 60.3

45.2

4.56

57.2

43.9

5.06

53.8

42.5

5.60

50.5

41.1

6.23

45.1

38.9

6.86

39.9

36.7

7.57

62

59.7

57.0

4.55

56.7

55.4

5.05

53.4

53.4

5.60

51.2

51.2

6.24

47.2

47.2

6.92

43.1

43.1

7.69

57

57.8

57.8

4.52

55.1

55.1

5.02

53.2

53.2

5.59

51.2

51.2

6.24

47.4

47.4

6.92

43.3

43.3

7.69

Multipliers for Determining the Performance With Other Indoor Sections

Indoor

Section

Size

Cooling

Indoor

Section

Size

Cooling

Capacity

Power

Capacity

Power

CC5A/CD5AA

060

0.96

0.99

CK5PA

060

1.02

0.99

CC5A/CD5AW

060

1.02

1.02

CK5PT

060

1.02

0.99

CD5PX

060

1.03

1.02

CK5PX

060

1.02

0.97

CE3AA

060

1.00

1.00

COILS + 315(A,J)AV066135 VARIABLE SPEED FURNACE

CK3BA

060

1.00

1.00

CC5A/CD5AA

060

0.98

0.98

CK5A/CK5BA

060

1.00

1.00

CC5A/CD5AW

060

1.02

0.99

CK5A/CK5BT

060

1.00

1.00

CE3AA

060

1.02

0.98

CK5A/CK5BX

060

1.02

1.00

CK3BA

060

1.02

0.99

CK5PA

060

1.00

1.00

CK5A/CK5BA

060

1.02

0.99

CK5PT

060

1.00

1.00

CK5A/CK5BT

060

1.02

0.99

CK5PX

060

1.02

1.00

CK5A/CK5BX

060

1.02

0.97

F(A,B)4(A,B)N(F,B,C)

060

1.00

1.03

CK5PA

060

1.02

0.99

FB4(A,B)NB

070

1.02

1.01

CK5PT

060

1.02

0.99

FC4(B,C)N(F,B)

060

1.00

1.04

CK5PX

060

1.02

0.97

FC4(B,C)NB

070

1.02

1.02

COILS + 315(A,J)AV066155 VARIABLE SPEED FURNACE

FG3AAA

060

0.98

0.99

CC5A/CD5AA

060

0.98

0.97

FK4(C,D)NB

006

1.02

0.97

CC5A/CD5AW

060

1.00

FV4(A,B)NB

006

1.02

0.97

CD5PX

060

1.03

0.98

FX4(A,B)NB

060

0.98

0.99

CE3AA

060

1.02

0.97

COILS + 315(A,J)AV066110 VARIABLE SPEED FURNACE

CK3BA

060

1.02

0.98

CC5A/CD5AA

060

0.98

0.98

CK5A/CK5BA

060

1.02

0.98

CD5PX

060

1.03

0.99

CK5A/CK5BT

060

1.02

0.98

CE3AA

060

1.02

0.98

CK5A/CK5BX

060

1.02

0.97

CK3BA

060

1.02

0.99

CK5PA

060

1.02

0.98

CK5A/CK5BA

060

1.02

0.99

CK5PT

060

1.02

0.98

CK5A/CK5BT

060

1.02

0.99

CK5PX

060

1.02

0.97

CK5A/CK5BX

060

1.02

0.97