Klimaire KSIL024-H219 Service Manual User Manual
Page 55

53
9.2.3 Fan speed has been out of control diagnosis
9.2.4 Open or short circuit of temperature sensor diagnosis and solution
Yes
Replace the outdoor PCB
Yes
Check the connections between
the sensors and the PCB. Are the
connections good?
Replace the sensor and check if
the errors happen again?
Is the fan motor connector and
connection good?
The unit does not work normally
Turn off the unit, rotate the cross
fan. Does it rotate freely?
No
Disassemble the connection between
fan and motor, check if the bearing is
normal. If not, change the bearing. If
yes, follow the below step.
Yes
No
Yes
Is the voltage being applied to the fan
motor?
Yes
Shut off the power supply and turn on it 5s later
Replace the fan motor
Replace the PCB