Klimaire KSIL024-H219 Service Manual User Manual
Page 43

41
+5.0
+4.5
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
H
G
H
F
E
D
C
B
A
+0.5
While
Temp. zone
A
B
C
D
E
F
G
Frequency
F10
F9
F8
F7
F5
F3
F1
∆
T=0 as factory setting.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F10.
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts-
∆
T >11 ºF, the compressor will stop)
Meanwhile, the compressor running frequency is limited by the current.