8.5.6 Indoor fan operation rule.

1)

In cooling mode, indoor fan runs all the time and the speed can be selected as high,

medium, low and auto.

2)

Auto fan in cooling mode acts as follow:

8.5.7 Condenser high temperature protection function(in cooling and drying mode)

If T3>60℃ for 5 seconds, compressor will stop immediately, and the machine will not resume until T3<52℃.

8.6 Drying mode

8.6.1 Indoor fan speed is fixed at breeze grade and can’t be changed. The horizontal angle is the same as in

cooling mode.

8.6.2 Room overlow temperature protection

In drying mode, if room temperature is lower than 10℃, compressor will stop and not resume until room

temperature climbs up to 12℃.

8.6.3 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit frequency limit

are valid, and they are the same as that in cooling mode.

8.6.4 Horizontal louver action is the same as that in cooling mode.

8.7 Heating mode

8.7.1 Indoor fan action:

1) Anti-cold-wind

function.

2)

If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127

seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is

available.

3) If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and

anti-cold-wind is disabled.

44

38

37

34
33

24

17

setting fan speed

low fan

breeze

super breeze

fan stop

E

vapo

ra

tor te

mp

Ԩ

Δ

T

=

(r

oo

m t

e

m

p

)

– (set

ting

Te

mp

)

medium

4.0

3.0

1.5

1.0

high

low