4.0 Appendix A: Compatible Addressable Devices
Table 9:System Sensor Compatible Addressable Devices
Model
Description
Typical Current
Draw µA
1251
Ionization type smoke detector
300
1251B
Ionization type smoke detector
300
2251
Photoelectric type smoke detector
300
2251B
Photoelectric type smoke detector
360
2251T
Photoelectric type smoke detector w/ thermal element
300
2251TB
Photoelectric type smoke detector w/ thermal element
360
2251TM
Acclimate Photo-Thermal Detector
300
2251TMB
Acclimate Photo-Thermal Detector
360
5251P
Thermal detector
200
5251B
Thermal detector
300
5251RP
Thermal detector w/ rate of rise
200
5251RB
Thermal detector w/ rate of rise
300
5251H
High Temperature Thermal detector
300
IM-10
10 Input Monitor Module
3.50 mA
CR-6
6 Relay Control Module
1.45 mA
SC-6
6 Supervised Control Module
2.25 mA
CZ-6
6 Zone Conventional Interface Module
2.00 mA
M500DM
Dual Input Monitor Module
300
M500M
Monitor module, Classes A/B initiating
300
M501M
Mini Monitor module, Class B initiating
300
M502M
Monitor Module for 2- wire smoke detectors Classes A/B
initiating
200
M500S
Control module
300
M500R
Relay Module
300
M500X
Fault isolator module
450