Evax system wiring, 5 maximum wiring length for addressable circuits, 6 maximum wiring length for bell circuits – Harrington Signal HS-3200 - Install Manual User Manual
Page 25: 5 maximum wiring length, 6 maximum wiring length for

HS-3100/3200 Installation Manual
19
EVAX System Wiring
3.5 Maximum Wiring Length for Addressable Circuits
Note: Distances noted in this table account for the total length of wire, from the panel to furthest device
and back to the panel.
3.6 Maximum Wiring Length for Bell Circuits
Note: Distances noted in this table account for the total length of wire, from the panel to furthest device and
back to the panel.
Gauge
Belden No. Maximum Distance
18
9571
975m (3200 ft)
16
9572
1400m (4600 ft)
14
9580
2435m (8000 ft)
12
9582
3045m (10000 ft)
12AWG
14AWG
16AWG
18AWG
Max R
Max I
m
ft
m
ft
m
ft
m
ft
8.00
0.25
768
2519
483
1584
304
996
191
627
4.00
0.5
384
1259
241
792
152
498
95
313
2.67
0.75
256
840
161
528
101
332
64
209
2.00
1
192
630
121
396
76
249
48
157
1.60
1.25
154
504
97
317
61
199
38
125
1.33
1.5
128
420
80
264
51
166
32
104
1.14
1.75
110
360
69
226
43
142
27
90
1.00
2
96
315
60
198
38
125
24
78