Dimensions — Weights

0

30

60

90

120

150 170 gpm

0 114 228 342 456 570

646

lpm

3

/

4

” - 2” (20 - 50mm)**

A

C

D

Pressure Loss

Flow Rate

Installation

Atmospheric Vacuum Breaker must be installed 6" (152mm)

above the highest point of the downstream piping. There can be

no shutoff valves downstream of an AVB. The AVB should not be

subjected to continuous pressure for more than 12 hours per ASSE

Std. 1001.

size (DN)

DimeNsioNs

weight

A

C

D

in.

mm**

in.

mm

in.

mm

in.

mm

lbs.

kgs.

3

4

20

2

1

4

57

1

7

8

48

1

1

2

38

1.13

.51

1

25

2

7

8

73

2

1

8

54

1

11

16

43

1.75

.79

1

1

4

32

2

7

8

73

2

1

8

54

1

13

16

46

2.13

.96

1

1

2

40

3

5

8

92

2

7

16

62

2

3

16

56

3.63

1.64

2

50

4

1

8

105

2

7

8

73

2

1

2

64

5.25

2.38

Capacities

kPa psi
82 12

62 9

41 6

21 3

0 0

3

/

4

1”

1

1

/

4

1

1

/

2

2”

ES-188A 1223

© 2012 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca

A Watts Water Technologies Company

** Metric Dimensions are nominal pipe diameter. This product

is produced with NPT threaded end connections.