Watts LFWDS User Manual
Series lfwds, Lead free, Floodsafe

Series LFWDS
FloodSafe
®
Water Detector Shutoff
Sizes:
3
⁄
4
" and 1" (20 and 25mm)
Series LFWDS Floodsafe
®
Water Detector Shutoff is a safety
valve that protects the home or business owner from cata-
strophic damage due to a water heater leak. The Series LFWDS
detects the presence of water on the floor (or in a drain pan)
beneath the water heater and automatically shuts off the water
supply and power source to the water heater. The LFWDS fea-
tures Lead Free* construction to comply with Lead Free* instal-
lation requirements.
Features:
•
Testable and Resettable:
The FloodSafe
®
Water Detector Shutoff
can be easily
reset by the contractor, home or
business owner or plumbing inspector to assure proper
operation.
•	Lead	Free*	cast	copper	silicon	alloy	valve	body	construction
•		Easily	installed	on	new	or	existing	water	heaters.
 – No special piping is required.
 – Supplied with a Water Dam for concrete, linoleum, 
tile or other hard surface flooring.
– Sized for
3
⁄
4
" or 1" (20 or 25mm) water supply lines.
– Secure interlocking connector cables are unique
to each connecting device.
– Powered by a safe low-voltage power supply that plugs into
a standard 120 VAC wall outlet and is wired using standard
thermostat cable (supplied by installer).
• Employs state-of-the-art water detection technology (no
terminals to corrode or to impair operation).
•		Provides	contacts	for	monitored	alarm	detection	systems.
•		Power	Cutout	Modules	for	the	standing	pilot	gas	fired	water	
heaters retain thermocouple circuit in the event of momentary
power outage.
Mechanical
	 Maximum	Pressure:	150psi	(10.3	bar)
	 Maximum	Temperature:	210°F	(99°C)
Electrical
 120 VAC, 70mA, 60Hz
 Current draw: 50mA
	 Maximum	Electric	Water	Heater	current	rating:	30A
Specifications
The contractor shall install an electronically actuated resettable
shutoff valve on the cold water supply of the water heater, as
indicated on the drawing.
The electronically actuated valve shall be a full flow valve that 
closes upon detection of water at the water detector pad sup-
plied with the valve. Lead Free* valves shall be constructed
using Lead Free* materials. Lead Free* Water Detector Shutoff
valves shall comply with state codes and standards, where
applicable, requiring reduced lead content. A water detector
pad shall be installed on the floor beneath the water heater or
in a drain pan supplied by the contractor. The water detector
pad shall be supplied with an integral cable with connector to
connect to the valve control unit. The water detector pad shall
be an electronic sensing device.
The electronically actuated valve shall act to shut off both the 
water supply and the power to the water heater simultaneously
upon detection of water.
A visual and audible indication of actuation shall be initiated 
and normally open contacts suitable for connection to remote
monitored alarm actuation shall close. 
(Optional: The remote alarm contacts will be connected to a 
building alarm system by the alarm contractor).
The valve shall be provided with an integral control unit, a 
water dam, a power supply and a power cutout module in
addition to the water detection pad.
For Residential and Commercial Applications
Models
LFWDS-SP-L Standing Pilot - left-hand thread
LFWDS-SP-R Standing Pilot - right-hand thread
LFWDS-E220	 Electric	-	220	VAC
LFWDS-SI 
Spark Ignition/Oil Fired
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, 
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
LEAD FREE
*
Job Name –––––––––––––––––––––––––––––––––––––––––––
Contractor ––––––––––––––––––––––––––––––––––––––––––––
Job Location –––––––––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Engineer –––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Representative ––––––––––––––––––––––––––––––––––––––––
ES-LFWDS
LFWDS-SP-L
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.