Table 1B —524J***A Physical Data, SI — Cooling Units
UNIT 524J*
25A
28A
30A
NOMINAL CAPACITY (kW)
70
87
105
OPERATING WEIGHT (kg)
Base Unit with TXV
331
477
482
Plenum
102
148
148
FANS
Qty...Diam. (mm)
2...381
2...457
2...457
Nominal Airflow (L/s)
3775
4119
5663
Airflow Range (L/s)
2831 – 4719
3539 – 5899
4247 – 7079
Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60
3.73
5.60
7.46
575---3---60
3.73
5.60
7.46
Motor Speed (r/s)
208/230---3---60 and 460---3---60
29.1
29.1
29.1
575---3---60
29.1
29.3
29.3
REFRIGERANT
R---410A
Operating charge (kg)
(approx per circuit)*
1.59
2.04
2.27
DIRECT---EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag)
4481
Face Area (sq m)
1.85
2.30
2.77
No. of Splits
2
2
2
No. of Circuits per Split
18
20
24
Split Type...Percentage
Face...50/50
Rows...Fins/m
4...591
4...591
4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)
2...1
1
/
8
2...1
3
/
8
2...1
3
/
8
DX Coil — Liquid Refrigerant (ODF)
2...
5
/
8
Steam Coil, In (MPT)
1...2
1
/
2
Steam Coil, Out (MPT)
1...
1
/
2
Hot Water Coil, In (MPT)
1...2
Hot Water Coil, Out (MPT)
1...2
Condensate (PVC)
1...1
1
/
4
ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (mm.)
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 610 x 51
4...508 x 635 x 51
Access Location
Either Side
STEAM COIL**
Max Working Pressure (kPag at 126° C)
138
Total Face Area (sq m)
1.24
1.39
1.39
Rows...Fins/m
1...394
1...394
1...394
HOT WATER COIL**
Max Working Pressure (kPag)
1034
Total Face Area (sq m)
1.24
1.39
1.39
Rows...Fins/m
2...335
2...335
2...335
Water Volume
(L)
52.6
54.1
(m
3
)
0.052
0.054
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
**
Field installed accessory only.
524J