Weidmuller WI-I/O 9-L-R: Wireless I/O Receiver Quick Start Guide v1.7 User Manual
Page 7

WI-I/O 9-L Receiver Unit Quick Start Guide
WI-I/O 9-L Receiver Unit Guide v1.7
page 7 of 8
Thank you for selecting the WI-I/O 9-L receiver for your telemetry needs. We trust it will give you many years of
valuable service. To ensure your WI-I/O 9-L receiver enjoys a long life, double-check ALL your connections with the
user’s manual before powering on the unit.
WARNING
: Incorrect termination of supply wires may cause internal damage and will void warranty.
Exposure to RF energy is an important safety consideration. The FCC has adopted a safety standard for human
exposure to radio frequency electromagnetic energy emitted by FCC regulated equipment as a result of its actions in
Docket 93-62 and OET Bulletin 65 Edition 97-01.
FCC Notice when used in USA: WI-I/O 9-L-R Module
Part
Additional information
15
This device has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part15 of the FCC rules (Code of Federal Regulations 47CFR Part 15). Operation is subject to the condition
that this device does not cause harmful interference.
90
This device has been type accepted for operation by the FCC in accordance with Part90 of the FCC rules
(47CFR Part 90). See the label on the unit for the specific FCC ID and any other certification designations.
Industry Canada: Wireless I/O Module
RSS-119 - This device has been type accepted for operation by Industry Canada in accordance with RSS-119 of the
Industry Canada rules. See the label on the unit for the specific Industry Canada certification number and any other
certification designations.
NOTE: Any changes or modifications not expressly approved by Weidmuller, Inc. P/L could void the user’s authority
to operate this equipment.
To operate this equipment legally the user must obtain a radio-operating license from the government agency. This is
done so the government can coordinate radio users in order to minimize interference.
Safety information - FCC Notice
This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference; and
This device must accept any interference received, including interference that may cause undesired operation
NOTE: This equipment is suitable for use in Class 1 Division 2 groups A, B and C or non-hazardous locations only.
Input/output
Number
Additional information
Digital outputs
3
Voltage-free contacts rated at 250 VAC, 1A.
2 for digital inputs and 1 for setpoint.
Status outputs
2
Separate System OK and communication failure output.
Analog output
1
16-bit resolution, 0.1% accuracy, single-ended source output.
Power supply
1
9-30 VDC 1 Amp CSA certified Class 2 power supply. For use in
Class 1 Div 2 explosive areas, the power supply must be
approved for Class 1 Div 2 use.
WARNING
: Explosion hazard - do not disconnect while circuit is
live unless area is known to be non-hazardous.
Radio receiver
1
High sensitivity FHSS UHF radio receiver.
Frequency
902 – 928 MHz
Actual frequency range depends on country.
Sensitivity
-110 dBm
At PER 8%.