Weidmuller WI I/O 9-4: Wireless I/O Transceiver 16DI-4DO/4DI-16DO v1.4 User Manual
Installation guide, Wi-i/o 9-4, Aerial installation

Weidmuller Inc., v1.4
WI-I/O 9-4
Installation Guide
FCC Notice
This device complies with Part 15.247 of the FCC Rules.
Operation is subject to the following two conditions:
1) This device may not cause harmful interference and
2) This device must accept any interference received, including
interference that may cause undesired operation
Aerial Installation
WI-I/O 9-4 Installation
Power supply may be: (A) 12-24VAC
(B) 15-30VDC
(C) Supply battery or 11-15VDC
(D) Solar panel with solar battery
Choose option and wire as shown
1m minimum
COLINEAR
ANTENNA
MAST
EARTH STAKE
IF GROUND CONDITIONS ARE
POOR, INSTALL MORE THAN
ONE STAKE
INSTALL AERIAL ABOVE
LOCAL OBSTRUCTIONS
ANT
WI-I/O
SURGE
ARRESTOR
(OPTIONAL)
COAXIAL CABLE
WEATHERPROOF
CONNECTORS WITH
“3M 23” TAPE
STRESS RELIEF LOOP
PROVIDE GOOD
GROUND
CONNECTION TO
MAST, MODULE
AND SURGE
ARRESTOR
GND
ANTENNA INSTALLATION
Antennas should be installed by experienced contractors.
OUTPUTS
RADIO TELEMETRY MODULE
D
IO
9
D
IO
10
D
IO
11
D
IO
12
D
IO
8
D
IO
7
C
O
M
D
O
4
D
O
3
D
O
2
D
O
1
S
O
L
G
N
D
B
A
T+
I/0
INPUTS
I/0
D
IO
3
D
IO
4
D
IO
5
D
IO
6
D
IO
2
D
IO
1
C
O
M
D
I
4
D
I
3
D
I
2
D
I
1
G
N
D
S
U
P
2
S
U
P
1
-
+
To Earth
Connection
DC Supply
15-30VDC
min 17VDC
for Battery
Charging
S
O
L
G
N
D
S
U
P
2
S
U
P
1
AC Supply 12-24VAC
min 15VAC for Battery
Charging.
Do not earth SUP1 or
SUP2 connections
12V Solar Panel
Supply max 20VDC
max 30W panel
2A
+ -
11-15VDC Supply or
Optional 12V Backup
Battery
to 12 Amphour for AC/DC
to 100 Amphour for Solar
+ -
Digital Output
Max 30VDC, 500mA
DC Relay Supply
DC Load
Digital Input
Voltage Free
Contact
OR
Transistor
Device
NOTES
1. DIO channels can be
wired as either inputs or
outputs.
2. In USA / Canada, all
I/O must be SELV.