Installation guide, Wi-i/o 9-2, Aerial installation

background image

Weidmuller Inc., v1.4

WI-I/O 9-2

Installation Guide

Aerial Installation

WI-I/O 9-2 Installation

Power supply: (A) 12-24VAC 1.5 Amp CSA Certified Class 2

(B) 15-30VDC 1.5 Amp CSA Certified Class 2

(C) Supply battery or 11-15VDC

(D) Solar panel with solar battery

Choose option and wire as shown

FCC Notice

This device complies with Part 15.247 of the FCC Rules.

Operation is subject to the following two conditions:

1) This device may not cause harmful interference and

2) This device must accept any interference received, including

interference that may cause undesired operation

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2

GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS ONLY

1m minimum

COLINEAR

ANTENNA

MAST

EARTH STAKE

IF GROUND CONDITION IS POOR

INSTALL MORE THAN 1

STAKE

INSTALL AERIAL ABOVE

LOCAL OBSTRUCTIONS

ANT

WI-I/O

SURGE

ARRESTOR

(OPTIONAL)

COAXIAL CABLE

WEATHERPROOF

CONNECTORS WITH

“3M 23” TAPE

STRESS RELIEF LOOP

PROVIDE GOOD

GROUND

CONNECTION TO

MAST, MODULE

AND SURGE

ARRESTOR

GND

ANTENNA INSTALLATION

Antennas should be installed by experienced contractors.

2A

-

-

+

-

+A

I 2

-

+A

I 1

+2

4V

D

I

3

S

O

L

D

I

2

D

I

1

G

N

D

C

O

M

D

I

4

S

U

P

2

S

U

P

1

B

A

T+

A

I 3

+

A

I 4

+

A

I 6

+

A

I 5

+

G

N

D

+

24

V

D

O

T

C

O

M

C

O

M

OUTPUT

1

2

3

4

INPUTS

WI-I/O 9-2

RADIO TELEMETRY MODULE

+ -

+ -

Digital Output

Max 30VDC, 500mA

DC Relay Supply

11-15VDC Supply or

Optional 12V Backup

Battery

to 12 Amphour for AC/DC

to 100 Amphour for Solar

+ -

+

Ext. Powered

AnalogTransducer

Loop

Powered

Analog

Transducer

Digital Input

Voltage Free

Contact

OR

Transistor

Device

To Earth

Connection

DC Supply

15-30VDC

min 17VDC

for Battery

Charging

S

O

L

G

N

D

S

U

P

2

S

U

P

1

AC Supply

12-24VAC

min 15VAC

for Battery

Charging.

Do not earth

SUP1 or

SUP2

connections

12V Solar

Panel Supply

max 20VDC

max 30W

panel

DC Load

NOTES

1. All I/O must be SELV.

CAUTION!

For continued

protection against

risk of fire, replace

the module fuse only

with the same type

and rating

WARNING!

EXPLOSION HAZARD

DO NOT DISCONNECT

WHILE CIRCUIT IS LIVE

UNLESS AREA IS

KNOWN TO BE NON –

HAZARDOUS