beautypg.com

Electrical considerations, 2 electrical requirements for the system – WarmlyYours TempZone Floor Heating Cable (Twin) User Manual

Page 10

background image

Electrical Considerations

SECTION 4

7

4.2 Electrical Requirements for the System

Where required, all electrical work for the floor heating cable installation must be done by a qualified, licensed electrician

in accordance with local building and electrical codes and the National Electrical Code (NEC), especially Article 424, Part

IX of the NEC, ANSI/NFPA 70 and Section 62 of the Canadian Electrical Code (CEC), Part I, as well as any other applicable

statutory requirements.

WarmlyYours recommends the following controls and accessories for the TempZone™ Floor Heating Cable (Twin):

• SmartStat™ Programmable Thermostat or EasyStat™ Thermostat. Both of these units feature a Listed Class-A GFCI

and a floor sensor to regulate the actual temperature of the floor

• Non-GFCI circuit breaker

In most installations, a Class-A GFCI is required by national and local codes for protection against ground leakage currents.

A Class-A GFCI is included with the Smartstat™ and Easystat™ thermostats. If not using a WarmlyYours thermostat, a

Class-A GFCI thermostat or circuit breaker may be needed.

The TempZone™ Floor Heating Cable (Twin) should be connected to a non-GFCI circuit breaker for complete disconnection

on all poles with minimum 0.12 inch disconnection distance.

The thermostat should be installed in a double-gang box with a single-gang mud ring flush with the wall at a height of

approximately 5 feet or eye level for easy access and operation. The floor sensor cable and the TempZone™ Floor Heating

Cable (Twin) cold leads shall be routed to the thermostat in separate UL Listed conduits if conduit is required by local and

national electric codes.

If the floor heating cable load exceeds the 15-amp thermostat power rating, consult WarmlyYours for information on

alternative solutions using master thermostats and power modules.