beautypg.com

TCI KRF User Manual

Page 32

background image

26


Typical circuit diagram













Technical data and measuring conditions

Rated voltage V

R

530/310 V AC, 50/60 Hz

Read current I

R

Referred to 40°C ambient temperature

Test voltage V

test

2280 V DC, 2 s (line/line)
2690 V DC, 2 s (lines, case)

1.5 · I

R

for 3 min per hour or

2.5 · I

R

for 30 s per hour

Overload capability (thermal)

At V

R

, 50 Hz

Leakage current I

leak

25/100/21 (-25°C/+100°C/21 days damp heat test)

Climatic category (IEC 60068-1)

UL 1283; CSA C22.2 No.8
(Type: 500/290 V)



Characteristics and part numbers

V

R

AC
V

I

R


A

I

leak


mA

R

typ

µΩ

Approx
weight
kg

Part Number

Approvals

500/290V

530/310

150

< 20

140

13

KRF0150ACB

X

X

600

< 20

52

22

KRF0600ACB

X

X

1000

< 20

33

28

KRF1000ACB

X

X

1600

< 20

22

34

KRF1600ACB

X

X

2500

< 20

15

105

KRF2500ACB

X

X


X = approval granted