Installation

o

utSide

f

reSh

-a

ir

c

onnection

:

This Heater must have adequate air for proper combustion in the room that it is installed.
A Fresh-air intake is strongly recommended for all installations
. Failure to install intake air may

figure 7: outside air connection.

e

xhauSt

a

nd

f

reSh

a

ir

i

ntake

l

ocationS

:

result in improper combustion as well as the unit smoking

during power failures.
The inlet to the intake must be below and a minimum of 12”

(30cm) away from the unit exhaust outlet.
Outside fresh air is mandatory when installing this

unit in airtight homes and mobile homes.
When connecting to an outside fresh air source, do not use

plastic or combustible pipe. A 3” minimum (76 mm) ID

(inside diameter) steel, aluminum or copper pipe or ducting

should be used. The inlet must have a screen installed. It is

recommended, when you are installing a fresh air system, to

keep the number of bends in the pipe to a minimum.

3" ID

(76 mm)

Optional

Elbow

Outside

Wall

figure 8: Gci60 inlet and outlet location.

This unit uses a 4” exhaust vent.

EXHAUST:

Base of unit to center of flue

16

1

/

4

” (413 mm)

Center of unit to center of flue

9

5

/

8

” (245 mm)

FRESH AIR INTAKE.

Base of unit to center of intake

5

1

/

8

” (130 mm)

Center of unit to center of intake

5” (128 mm)

3.000

16.373

5.120

4.000

4.952

9.624

Hampton GCI60 Cast Pellet Insert Technical Manual