6 720 608 263

Installation instructions

11

3.6

Venting

3.6.1

Vent material and specifications

Establish vent clearances that comply with the vent
manufacturer's specifications. In all cases follow local
codes.
Note: Listed thimbles or collars are necessary to pass
through wall and ceiling partitions. If the vent system
passes through combustible areas where the vent
clearance requirements cannot be maintained, it is
permissible to chase straight sections of sealed 3 inch
single wall vent through 4 inch (or greater) Type-B vent.
The distance to combustibles using this chase
technique is 1 inch (check local codes).

Vent lengths

The appliance should be located as close to the point
of termination as possible. The maximum vent length is
26 feet (8 m) with one 90 degree elbow. Subtract 2½
feet from the total vent length for each additional 90°
elbow used (a maximum of three 90° elbows are

permitted in the total vent length), or subtract 11/4
feet for every 45° elbow used. Horizontal sections of
vent must pitch upwards from heater ¼" for every foot
of horizontal length, to prevent the pooling of
condensate, and be supported at 4 foot intervals with
overhead hangers. See Table 2.

Minimum exhaust vent size and length

Fig. 8

Minimum exhaust vent length

Fig. 9

Maximum vent and combustion air lengths

Vent material

The 2400 E requires 3 or 4 inch sealed single wall
stainless steel vent pipe (AL29-4C). Use of any other
vent material will void the manufactures warranty and

Danger: Do not combination vent this
appliance with any other appliance.

Warning: Do not reduce the vent
(exhaust and combustion) pipe sizes
and do not common vent with any other
vented appliance or stove.

Warning: Failure to vent the exhaust
gases to the outside with sealed
stainless steel vent pipe (AL29-4C)
may result in dangerous flue gases
filling the space in which it is installed.

Warning: Single wall exhaust pipe
MUST be chased through double wall
Type-B vent when passing through an
unconditioned space.

Warning: The vent system must be
installed by a qualified individual in
accordance with these instructions. If
improperly installed a hazardous
condition such as explosion or carbon
monoxide poisoning could result.
Bosch Water Heating will not be
responsible for improperly installed
appliances.

Warning: Type-B vent must never be
used as the actual exhaust vent system
for the appliance, because it is not gas
tight. This will create a serious health
hazard and void the warranty.

Diameter

Minimum

length

Maximum

length

Material

Exhaust Vent

3 or 4

inches

3 feet

26 feet with

1 90°

elbow

Sealed single

wall stainless

steel (AL29-4C)

Intake Vent

3 or 4

inches

1 90° elbow

26 feet with

1 90°

elbow

Sealed

aluminum flex,

PVC or any

other rigid or

semi rigid pipe

Table 2 Venting specifications

The minimum exhaust vent length is
3 feet.
The use of a 90 degree elbow is
equivalent to 2 ½ ft in vent length.
The use of 45 degree elbow is
equivalent to 1 ¼ ft in vent length.

Reduce maximum
length 2 ½ ft for
each 90 elbow after
the first one and 1 ¼
ft for each 45 elbow.