beautypg.com

Vi. 2, 3, or 4-door mantrap “b” setup – SDC UR2-4 User Manual

Page 24

background image

P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV 03-11 Page 7

VI. 2, 3, or 4-Door Mantrap “B” Setup

Follow the installation steps below before applying power to the UR4-8.
Refer to the MANTRAP “B” MODE wiring diagram on Page 8.

NOTE: It is assumed that the UR4-8 and locking hardware share the
same power supply.

Mantrap “B” Standard Operation:
All doors are normally closed and locked. Each door may be individually
unlocked using the Access Control System or a remote release.
Unlocking any door causes the other doors to be incapable of being
unlocked until the unlocked door returns to its normal state.

The door unlock time will be determined by the Access Control System
and by Dip Switches 2-1 through 2-4 (See Step 1).

Step 1 – Set Dip Switches

The dip switch settings below are an example of a typical Mantrap B
setup as shown on Page 8. Adjust the dip switch settings as needed.

Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.

Use the red WET/DRY Selection Jumpers to configure each output.
Refer to Page 2 of this instruction for selection procedure.

On the typical Mantrap B wiring diagram, the Lock Relays (Outputs 1, 3,
5, & 7) are configured to be wet outputs.

The Monitoring Relays (Outputs 2, 4, 6, & 8) are dry.

NOTE: It is recommended that any unused relays be configured as dry
outputs.

SW1 -1 = ON

No rmally Lo cks Do o r # 1. This switch must be set ON fo r
M antrap "B " M o de

SW1 -2 = ON

No rmally Lo cks Do o r # 2. This switch must be set ON fo r
M antrap "B " M o de

SW1 -3 = ON

No rmally Lo cks Do o r # 3. This switch must be set ON fo r
M antrap "B " M o de

SW1 -4 = ON

No rmally Lo cks Do o r # 4. This switch must be set ON fo r
M antrap "B " M o de

SW1 -5 = OFF
SW1 -6 = OFF
SW1 -7 = OFF
SW1 -8 = OFF

This switch must be set OFF fo r M antrap "B " M o de

SW2-1 = ON

SW2-2 = OFF

SW2-3 = OFF

SW2-4 = OFF

SW2-5 = OFF

Sets the po larity o f the Do o r M o nito ring Inputs when the
do o r is in the CLOSED and/o r LOCKED po sitio n.
{OFF = N/O; ON = N/C}

SW2-6 = OFF

Sets the po larity o f A ccess Co ntro l Inputs when the switch
is in a no rmal (resting) state. {OFF = N/O; ON = N/C}

SW2-7 = OFF

Sets the o peratio n o f all the M o nito ring Relay Outputs.
{OFF = Relay will fo llo w the Do o r M o nito ring Input;
ON = Relay will fo llo w the Lo ck Output Relay}

SW2-8 = ON

Switches the UR bo ard between Interlo ck M o de o r Co ntro l
M o de. This switch must be set ON.

SW2-1 thro ugh 2-4 set the unlo ck time o f the Lo ck Relay.
N O T E

: This is in additio n to yo ur A ccess Co ntro l System

unlo ck time.
SW2-1 ON = 5 sec., OFF = 0 sec.;
SW2-2 ON = 1 0 sec., OFF = 0 sec.;
SW2-3 ON = 20 sec., OFF = 0 sec.;
SW2-4 ON = 30 sec., OFF = 0 sec.;
Switch times are additive. {A ll OFF = 1 sec.; A ll ON = 65
sec.}

Step 3. Terminate the Lock Power Wiring

Follow the typical Mantrap B wiring diagram for fail-safe or fail-secure
locks. Be careful to observe lock voltage polarity.

NOTE: All low voltage wiring shall be 18-gauge minimum. The minimum
lock power wire gauge shall be determined by the SDC wire gauge chart.
Signal wire shall be 22-guage minimum.

Step 4. Terminate the Access Control and Door
Monitoring Inputs

Connect the Door Monitoring Switches to input terminals A1, B1, C1, &
D1. This is a required connection for all door stations being used.

Connect Access Control or remote releases to input terminals A2, B2, C2,
& D2. This is a required connection for all door stations being used.

Door Monitoring and Access Control inputs should be dry, Normally Open
or Normally Closed switches, depending on the configuration of Dip
Switches 2-5 and 2-6, respectively.

NOTE: Dip Switch 2-5 configures the normal state of the Door Monitoring
input when the door is in a CLOSED and/or LOCKED position. If
Normally Closed inputs are used, all unused inputs will need to be
shorted.

Step 5. Terminate Optional Inputs and Outputs

Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Page 2 for input descriptions.

Monitoring Relay Outputs – Each door station provides a non-fused,
SPDT monitoring relay. This output may be used to signal a Security
Panel or to activate a Remote Annunciator. The relay is configurable as a
Wet or Dry output (Step 2). The relay activation will follow the Lock Relay
or follow the Door Monitoring Input, depending on the configuration of Dip
Switch 2-7 (Step 1).

Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.

Before applying power, verify that all the connections are securely
terminated by gently pulling on each wire.

Terminate the voltage wiring to the Controller Power Input. Be careful to
observe polarity.

Verify that all the doors are closed & apply power to the controller.

Step 7. UR4-8 Controller Startup and Operation
Verification.

Verify the polarity of the Access Control & Door Monitoring Inputs by
observing the Status Lights located on the lower right of the UR4-8
controller.

Status Lights A1, B1, C1, & D1 will be OFF if Dip Switch 2-5 = OFF, or
will be ON if Dip Switch 2-5 = ON.

Status Lights A2, B2, C2, & D2 will be OFF if Dip Switch 2-6 = OFF, or
will be ON if Dip Switch 2-6 = ON.

Test the standard operation of the mantrap by unlocking any door using
the Access Control System or remote release. All other doors will be
incapable of being unlocked until the unlocked door returns to its normal
state (closed & locked).