16 • 65-2435RK CO Transmitter

7. Connect the detector leads to the detector terminal strip as shown in Table 4 and Figure 3,

Wiring the CO Transmitter to a Controller.

8. Reinstall the junction box cover.

9. Turn on or plug in incoming power at the power source end.

10. Turn on the controller.

CAUTION: Allow the replacement detector to warm up for 5 minutes before you continue with

the next step.

11. Set the null potentiometer on the amplifier as described in the Setting the Null Potentiometer

section.

CAUTION: The null potentiometer must be set whenever the complete detector assembly is

changed or the hydrogen compensation may not work properly.

12. Calibrate the replacement detector as described in the Calibration section of this manual.
13. Secure the junction box cover to the junction box.

Table 4: Connecting the Replacement CO Detector to the Amplifier

CO Detector Lead

Amplifier

Interconnect Terminal Strip

Black

BLK

Green

GRN

Brown

BRN

White

WHT

Red

RED