65-2330RK H
2
S Transmitter • 1
Overview
This manual describes the 65-2330RK hydrogen sulfide (H
2
S) transmitter. This manual
also describes how to install, start up, maintain, and calibrate the transmitter when using
it with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the H
2
S transmitter. See the controller operator’s manual for
information specific to the controller.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
manual.
Table 1 lists specifications for the H
2
S transmitter.
WARNING: When using the 65-2330RK, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the 65-2330RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 65-2330RK as described in this manual.
Table 1: Specifications
Target Gas
Hydrogen sulfide (H
2
S)
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
0 to 100 PPM (parts per million)
Accuracy
± 5% of reading or ± 2 ppm H
2
S (whichever is greater)
Response Time
90% in 30 seconds
Operating Temperature
-40°F to 104°F (-40°C to 40°C)