Practical instrument electronics, Accessories, Warranty – Practical Instrument Electronics 334Plus User Manual
Page 10: Stroking valves
![background image](/manuals/570427/10/background.png)
Practical Instrument Electronics
82 East Main Street Suite 3.14 • Webster, NY 14580 Tel: 585.872.9350 • Fax: 585.872.2638 • [email protected] • www.piecal.com
Page 10
Accessories
AC ADAPTOR (200 to 240 VAC)
Part No. 020-0100
AC ADAPTOR (100 to 120 VAC)
Part No. 020-0101
Ni-MH 1 Hour Charger w/4 Ni-MH AA Batteries
Part No. 020-0103
Warranty
Our equipment is warranted against defective material and workmanship (excluding batteries) for a
period of three years from the date of shipment. Claims under warranty can be made by returning
the equipment prepaid to our factory. The equipment will be repaired, replaced or adjusted at our
option. The liability of Practical Instrument Electronics (PIE) is restricted to that given under our
warranty. No responsibility is accepted for damage, loss or other expense incurred through sale or
use of our equipment. Under no condition shall Practical Instrument Electronics, Inc. be liable for any
special, incidental or consequential damage.
SETTING UP VALVES
When setting up a valve it is important to correctly set the end stops. Use the PIECAL 334Plus to
supply the 4 to 20 mA control signal to stroke the valve. Select “SOURCE” and the PIECAL 334Plus
will use the internal power source for outputting current or switch to 2-WIRE SIMULATOR to stroke
a valve using any pre-existing installed loop power supply as the power source.
Example:
1) Disconnect the 4-20 mA control wires from the Current-to Pressure (I/P) converter or the actuator.
2) Connect the PIECAL 334Plus following the connection diagrams on the previous pages for
Simulate 2-Wire Transmitters
3) Move the EZ-CHECK™ switch
e
to
“4.00 mA”/”0.0%” and adjust the fully closed stop on the
actuator.
4) Turn the PIECAL 334Plus’s knob
r
slowly counterclockwise and verify that the actuator and
valve don’t move. Repeat steps 3 & 4 until no movement is detected.
5) Move the EZ-CHECK™ switch
e
to
DIAL and quickly back to “4.00 mA”/”0.0%” then turn the
PIECAL 334Plus’s knob
r
clockwise. The actuator and valve should begin to move.
6) Move the EZ-CHECK™ switch
e
to
“20.00 mA”/”100.0%” and adjust the fully open stop on the
actuator.
7) Turn the PIECAL 334Plus’s knob
r
slowly clockwise and verify that the actuator and valve don’t
move. Repeat steps 6 & 7 until no movement is detected.
8) Move the EZ-CHECK™ switch
e
to
DIAL and quickly back to “20.00 mA”/”100.0%” then turn
the PIECAL 334Plus’s knob counterclockwise. The actuator and valve should begin to move
.
Stroking Valves