beautypg.com

Multiquip DCA150SSJU2 User Manual

Page 33

background image

DCA-150SSJU — PARTS AND OPERATION MANUAL — REV. #3 (09/07/01) — PAGE 33

The definitions below describe the controls and functions of
the DCA-150SSJU "

Engine Operating Panel " (Figure

10).

1.

Panel light - Normally used in dark places or at night.
When activated, panel will luminate. When the generator
is not in use, turn the panel light switch to the ‘OFF’
position.

2.

Panel light switch- When activated, will turn on control
panel light.

3.

Oil Pressure Gauge – During normal operation this
gauge be should read between 42 to 71 psi. When
starting the generator the oil pressure may read slightly
higher, but after the engine warms up the oil pressure
should return within the normal range.

4.

Water Temperature Gauge – During normal operation
this gauge be should read between 165

o

to 203

o

F.

5.

Charging Ammeter Gauge – Indicates the current
being supplied by the engine’s alternator which provides
current for generator’s control circuits and battery
charging system.

6.

Fuel Gauge - Indicates amount of diesel fuel available.

7.

Tachometer – Indicates engine speed in RPM’s for 60
Hz operation. This meter should indicate 1800 RPM’s
when the rated load is applied. In addition a built in hour
meter will record the number of operational hours that
the generator has been in use.

8.

Ignition Switch - This switch is used to turn on or off
the engine with a key.

9.

Throttle Handle - This handle controls the speed of
the engine (low or high).

10. Pre-Heat Button – This is to pre-heat the engine under

extreme cold conditions.

11. Water Temperature Indicator - This light indicates the

water temperature is too high and will shut down the
engine.

12. Oil Pressure Indicator - This light indicates the oil

pressure is either too high or too low and will shut down
the engine.

DCA-150SSJU — ENGINE OPERATING PANEL (With Key Switch)