page 34 — DCa25Usi2 60 hz generator • operation anD parts manUal — rev. #1 (02/28/14)

gEnEratOr ShUt-DOWn prOcEDUrES

emergenCY shUtDoWn proCeDUre

1. Place the

main, g.F.C.i., and aux. circuit breakers (Figure

50) in the OFF position.

2. Turn the ignition key (Figure 52) to the

STOP position.

Figure 52. Ingition Switch (Emergency)

normal shUtDoWn proCeDUre

To shutdown the generator, use the following procedure:
1. Place both the

main, gFCi and loaD circuit breakers

as shown in Figure 50 to the

OFF position..

Figure 50. Main, GFCI and Load

Circuit Breakers Off

2. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

3. Place the ignition switch (Figure 51) in the “

STOP

position, remove the key and store in a safe place.

Figure 51. Ingition (Switch Normal)

4. Verify that

all status LEDs on the MPEC display are

OFF (not lit).

5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

WARNING

never stop the engine suddenly except in an

emergency.