trOuBLEShOOtinG (GEnEratOr)

Troubleshooting (generator)

Symptom

possible problem

Solution

No Voltage Output

AC Voltmeter defective?

Check output voltage using a voltmeter.

Is wiring connection loose?

Check wiring and repair.

Is voltage regulator defective?

Replace if necessary.

Defective Rotating Rectifier?

Check and replace.

Defective Exciter Field?

Check and replace.

Low Voltage Output

Is engine speed correct?

Turn engine throttle lever to “High”.

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

Circuit Breaker Tripped

Short Circuit in load?

Check load and repair.

Over current?

Confirm load requirements and reduce.

Defective circuit breaker?

Check and replace.

Over current Relay actuated?

Confirm load requirement and replace.