beautypg.com

Installation – Multiquip GAC-9.7HZ User Manual

Page 15

background image

gaC9.7HZ 60 HZ geNeRaTOR • OpeRaTiON aNd paRTs maNual — Rev. #2 (03/31/10) — page 15

installatiOn

OuTdOOR iNsTallaTiON

If possible install the generator in a area that is free of

debris, bystanders, and overhead obstructions. Make sure

the generator is on secure level ground so that it cannot

slide or shift around.
The installation site must be relatively free from moisture

and dust. All electrical equipment should be protected from

excessive moisture. Failure to do will result in deterioration

of the insulation and will result in short circuits and

grounding.
Foreign materials such as dust, sand, lint and abrasive

materials have a tendency to cause excessive wear to

engine and alternator parts.

iNdOOR iNsTallaTiON

Exhaust gases from gas engines are extremely poisonous.

Whenever an engine is installed indoors the exhaust

fumes must be vented to the outside. The engine should

be installed at least two feet from any outside wall. Using

an exhaust pipe which is too long or too small can cause

excessive back pressure which will cause the engine to

heat excessively and possibly burn the valves.

plaCemeNT

The generator should always be placed on a flat level

surface when it is running.

DO NOT place the generator

on slopes, the possibility exists that the generator could

slide.

WaRNiNg

Pay close attention to ventilation when

operating the generator inside tunnels

and caves. The engine exhaust contains

noxious elements. Engine exhaust must

be routed to a ventilated area

daNgeR

An electric shock is apt to happen when

vibrators are used. Pay close attention to

handling when operating vibrators and

always use rubber boots and gloves to

insulate the body from a short circuit.

geNeRaTOR gROuNdiNg

To guard against electrical shock and possible damage to

the equipment, it is important to provide a good

eaRTH

ground.
Article 250 (Grounding) of the National Electrical Code

(NEC) provides guide lines for proper grounding and

specifies that the cable ground shall be connected to the

grounding system of the building as close to the point of

cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following

grounding requirements:
1. Use one of the following wire types to connect the

generator to earth ground.
a. Copper - 10 AWG (5.3 mm2) or larger.
b. Aluminum - 8 AWG (8.4 mm2) or larger.

2. When grounding the generator (Figure 2) connect the

ground cable between the lock washer and the nut on

the generator and tighten the nut fully. Connect the

other end of the ground cable to earth ground.

3. NEC article 250-52(c) specifies that the earth ground rod

should be buried a minimum of 8 ft. into the ground.

NOTICE

When connecting the generator to any buildings

electrical system

alWaYs consult with a licensed

electrician.