Page 2: Technical information, Duct averaging temperature sensors, Page 2 of 2

Model TE-705
Technical Information
TI.705-03
DUCT AVERAGING TEMPERATURE SENSORS
Page 2 of 2
TI.705-03
RoHS
Mounting
Location: Install the sensor in a location where it will sample the average
duct air temperature. Avoid areas where the air is stratified because these
areas can cause sensing errors.
TE-705: Refer to Figure 2 for mounting dimensions.
1. Drill a 7/16-inch (11 mm) hole into the duct where the sensor will
be installed.
2. Gently uncoil the sensor’s rigid probe and insert it into the duct.
3. Use the flange as a template to mark and drill two holes for the #8
self-tapping sheet metal screws (not provided).
4. Fasten the sensor to the duct with the sheet metal screws. Refer
to Figure 1.
Figure 1 - Installing the TE-705 Sensor
CHECKOUT
Allow the sensor to stabilize in the duct air stream for a minimum of five minutes
before taking a resistance measurement.
1. Disconnect the sensor lead wires from the controller.
2. Connect an ohmmeter across the lead wires.
3. Ensure that nominal resistance measurements are in accordance
with the resistance/temperature curves. (Refer to Tables 1 & 2.
For complete Resistance vs. Temperature tables, please refer to
TI.700-11 - Temperature Sensor section.)
4. Reconnect sensor lead wires to the controller.
5. Check operation of the complete control system.
MAINTENANCE
Regular maintenance of the total system is recommended to
assure sustained optimum performance.
FIELD REPAIR
None. Replace with a functional unit.
DIMENSIONAL DATA
Figure 2 - TE-705 Duct Averaging Temperature Sensor dimensions shown in
inches and millimeters (mm).
4.00" (102 mm)
2.00"
(51 mm)
1/2"
knockout
2.50"
(64 mm)
1/2" NPT fitting
1/2" knockout
Two #8 self-tapping
screws (not included)
System duct
or plenum
Probe
For Technical / Application Assistance call your nearest office
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
[email protected] • www.mamacsys.com
EUROPE
4200 Waterside Centre
Solihull Parkway
Birmingham • West Midlands
B37 7YN • United Kingdom
01384-271113 • Fax 01384-271114
AUSTRALIA
4 Armiger Court, Unit 2
Adelaide • S.A.
5088 • Australia
08-8395-4333 • Fax 08-8395-4433
CANADA
675 Cochrane Drive
East Tower • 6th Floor
Toronto • Ontario
L3R 0B8 • Canada
905-474-9215 • Fax 905-474-0876
ASIA
1 Fullerton Road #02-01
One Fullerton
Singapore • 049213
65-31581826 • Fax 65-31581826
MAMAC Systems, Inc., reserves the right to change any specifications
without notice to improve performance, reliability, or function of our products.