Drive control & communication – Lenze Tmd Series Drives Modbus Communications User Manual
Page 26
RG-TDMOD 22
Drive Control & Communication
Parameter No.
1
Tmd Register #
(hexadecimal
representation)
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory
Default
PV503
C14
64 (40H)
Operating Mode
0 Linear with Auto Boost
1 Square Law with Auto Boost
2 Linear with Constant V
min
Boost
3 Square Law with Constant V
min
Boost
4 Vector Speed Control
5 Vector Torque Control
6 Enhanced Linear Characteristic with Auto Boost
7 Enhanced Linear Characteristic with V
min
Boost
2
C15
65 (41H)
V/f Reference Point
250 - 9990 (25.0 - 999 Hz)
50.0 Hz
C16
66 (42H)
V
min
Boost
0 - 400 (0.0 - 40.0%)
4.0%
C17
67 (43H)
Frequency Threshold
0 - 2400 (0.0 - 240 Hz)
0.0 Hz
C18
68 (44H)
Chopper Frequency
0 4kHz
1 6kHz
2 8kHz
3 10kHz
2
69 (45H)
RESERVED
C21
70 (46H)
Slip Compensation
0 - 400 (0.0 - 40.0%)
0.0%
C22
71 (47H)
Current Limit
30 - 200%
200%
C24
72 (48H)
Accel Boost
0 - 200 (0.0 - 20.0%)
0.0%
C34
73 (49H)
Configuration
Analog Input
0 0...10V
1 0...5V
2 -10...+10V
3 0...20mA
4 4...20mA
5 4...20mA Monitored
0
74 (4AH)
RESERVED
C36
75 (4BH)
Voltage (DCB)
DC Injection Brake
0 - 500 (0.0 - 50.0%)
4.0%
C37
76 (4CH)
Fixed Setpoint 1 (JOG1)
0 - 2400 (0.0 - 240 Hz)
20.0 Hz
C38
77 (4DH)
Fixed Setpoint 2 (JOG2)
0 - 2400 (0.0 - 240 Hz)
30.0 Hz
C39
78 (4EH)
Fixed Setpoint 3 (JOG3)
0 - 2400 (0.0 - 240 Hz)
40.0 Hz
79 (4FH)
Not Used
80 (50H)
Not Used
C46
81 (51H)
Frequency Setpoint
0 - 2400 (0.0 - 240 Hz)
C47
82 (52H)
Torque Setpoint
0 - 400%
100%
83 (53H)
RESERVED
C50
84 (54H)
Output Frequency
0 - 2400 (0.0 - 240 Hz)
Read Only
85 (55H)
RESERVED
1 = The drive's programming code number; (2) = Two decimal places assumed.